Download Print this page

jablotron JA-180S Quick Start Manual page 2

Wireless fire detector

Advertisement

Warning: In the INST position, while the system is disarmed, it
is not protecting against fire. This setting also fully disables the
optical and acoustic indication on the detector itself.
J2: Alarm memory: If the event memory is ON at the time of alarm,
alarm LED indication continues even if normal conditions are restored.
The indication can be stopped by pressing the button (indication is
valid only for FIRE settings).
J3 and J4: Smoke / heat sensor participation
Optical smoke sensor: Smoke entry into the detector is indicated as a
pre-alarm state by the LED flashing. If the smoke threshold density is
exceeded, a siren sound is generated (indication is valid only for FIRE
settings).
Heat sensor: indication logic is equal to that of the smoke sensor.
Whenever the detector cover is opened, a tamper signal is sent.
Testing the detector
The functioning of the detector can be tested by pressing and
holding the test button (e.g. for 1 sec). This activates the siren and the
LED flashes (LED only if the fire reaction is set). The strength and
quality of detector signals can be measured by the control panel in
Service mode. During testing by the test button, the detector transmits
signals which can not trigger fire alarms in the control panel.
Warning: Never start a fire in a building to test the detector.
Instead, use smoke-simulating aerosols for realistic testing.
Silencing the siren during an alarm
During a fire alarm, the detector LED flashes 2 times briefly and the
built-in siren sounds (at a higher intensity than during a test). Under
these conditions the siren can be silenced by pressing the test button
for approx. 3 sec. The LED will continue to flash until the smoke clears
from the room (indication is valid only for FIRE settings).
However, if normal conditions are not restored within approx. 10
minutes (the smoke does not clear from the room or the temperature
does not drop), the siren re-activates.
Fault indication
The detector performs regular self-testing. If a fault is detected in the
detector, its LED will start to flash rapidly. In such a case, disconnect
the battery from the detector, and after about 20 secs, re-connect it. If
after a minute the LED still flashes, then send the detector off for
repair.
Battery replacement
The detector monitors its battery voltage and if too low, a transmission is
sent to the
control panel to inform the installer or user. The detector
The JA-180S wireless fire detector
continues to function but with a short LED flash every minute. Battery
replacement should not be delayed by more than two weeks. This
should be done by a qualified technician with the control panel in
Service mode.
After battery replacement, test the functioning of the detector using
its test button. Expired batteries should not be thrown into the garbage,
but disposed of according to local regulations.
Removing the detector from the system
If a detector is removed, the control panel announces the removal.
The detector has to be deleted in the control panel before intentional
removal.
Technical parameters
Voltage:
Lithium battery type or LST14500 (AA 3.6V / 2,4 Ah)
Typical battery lifetime
Communication band
Smoke detection
Smoke sensor sensitivity
Temperature detection
Fire-alarm temperature
Acoustic power of the built-in siren
Operational temperature range
Dimensions, weight
Complies with
ETSI EN 300220,EN 50130-4, EN 55022, EN 60950-1
Can be operated according to
JABLOTRON ALARMS a.s. hereby declares that the JA-180S is in
compliance with the essential requirements and other relevant provisions of
Directives 1999/5/EC and 1989/106/EC. The original of the conformity
assessment can be found at www.jablotron.com, Technical support
section.
Note: Although this product does not contain any harmful
materials we suggest you return the product to the dealer or
directly to the producer after use.
2
approx. 3 years
868.1 MHz, Jablotron protocol
optical, scattered light
m = 0.11 - 0.13 dB/m to EN 54-7
class A2 to EN 54-5
+60 °C to +70 °C
-10°C to +80 °C
diameter: 126 mm, height: 65 mm, 200 g
EN 54-7, EN 54-5 class A2, EN 54-25,
ERC REC 70-03
MHS53800
80 dB/m