Rear Panel Connections - Redback A 4506 Operating Manual

Table of Contents

Advertisement

3.0 Rear Panel Connections

Manufactured in Australia
By Altronic Distributors Pty. Ltd.
24V Auxilliary
www.altronics.com.au
Outputs
Model
AC Fuse (M205)
(Total maximum
A 4506
5A
Load = 1 Amp)
A4512
5A
Out
Out
1
2
- +
- +
CAUTION
!
RISK OF ELECTRIC SHOCK
OPEN BY QUALIFIED
240V AC
PERSONNEL ONLY
1
2
1
240V AC Input
Power is supplied via a 230V mains lead.
2
24V Auxiliary Outputs
These provide 24V DC at a maximum of 1 amp combined output current.
3
Low Battery and Mains Fail Contacts
Normally open contacts which close when a low battery condition occurs or when mains is no longer powering
the charger.
4
Battery Voltage Connection
This lead must be connected to the batteries via a separate cable to that which is connected to the battery +ve
and battery -ve binding posts. This separate lead accurately measures the voltage present at the batteries.
5
Battery -ve Connection
This is connected to the negative terminal of the battery.
6
Load -ve Connections
These binding posts are for the negative connection of the load(s). A maximum load of 50 amps per set of load
terminals.
7
Load +ve Connections
These binding posts are for the positive connection of the load(s). A maximum load of 50 amps per set of load
terminals.
8
Battery Isolate/Reset
This breaker can be used as an isolator to quickly disengage the batteries without having to disconnect leads. It
also acts as a safe guard against short circuits in the battery leads or reverse polarity connection.
9
Battery +ve Connection
This is connected to the positive terminal of the battery.
5
Separate cable to run to battery
for accurate voltage
indication.
THIS MUST BE
CONNECTED FOR
CORRECT OPERATION
Battery
Low
Mains
Voltage
Batt.
Fail
BATTERY (-VE)
Unit suitable for use with Sealed Lead Acid (SLA)
+ –
Contacts close
NOTE: Only use batteries of the same make and capacity.
on Alarm
Conditions
3
4
6
7
LOAD 1 (-VE)
LOAD 2 (-VE)
Please Note:
batteries only.
24V SYSTEM ONLY
Fig 2
LOAD 1 (+VE)
(max load current 50A)
WATERPROOF
100A
LOAD 2 (+VE)
(max load current 50A)
8
Redback® Proudly Made In Australia
Battery
Isolate/reset
BATTERY (+VE)
9
3

Advertisement

Table of Contents
loading

This manual is also suitable for:

A 4512