Factory Unit Controller Settings - Lennox LHT/LDT024 Installation Instructions Manual

Table of Contents

Advertisement

Factory Unit Controller Settings

Use the mobile service app to adjust parameters; menu
paths are shown in each table. Refer to the Unit Controller
manual provided with each unit.
Tables 12 and 13 show factory settings . Record adjusted
settings on the label located inside the compressor
access panel.
When field installing optional kits and accessories, the
Unit Controller must be configured to identify the option
before it will function. Refer to figures 35 and 36 to
determine whether the Unit Controller configuration I.D.
must change. To configure the option, use MAIN MENU >
SETUP > INSTALL menu path. Press SAVE until
CONFIGURATION ID 1 or 2 appears depending on the
option installed. Change the appropriate character in the
configuration I.D. For example, when an economizer is
installed using a single enthalpy sensor, change
configuration I.D. 1, the second character, to "S".
Units With BACnet Settings
RTU Menu > Network Integration > Network Setup Wizard > BACnet
MS/TP > See BACnet MAC Address
BACNET MAC ADDRESS:
Units With Room Sensor, CPC/LSE Gateway Settings
RTU Menu > Network Integration > Network Setup Wizard > SBUS >
Set SBUS Address
LCONN ADDRESS:
Units With LonTalk Settings
Use menu RTU Menu > Network Integration > Network Setup Wizard
> Set "LONTALK"
Page 42
TABLE 12
581038
TABLE 13
581037-01
LHT/LDT024, 036, 048, 060

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lht/ldt036Lht/ldt048Lht/ldt060

Table of Contents