2- Use a thermometer to accurately measure the
outdoor ambient temperature.
3- Apply the outdoor temperature to tables 5 through 8
to determine normal operating pressures. Pressures
are listed for sea level applications at 80°F dry bulb
and 67°F wet bulb return air.
4- Compare the normal operating pressures to the
pressures obtained from the gauges. Minor variations in
these pressures may be expected due to differences in
installations. Significant differences could mean that the
system is not properly charged or that a problem exists
with some component in the system. Correct any
system problems before proceeding.
5- If discharge pressure is high, remove refrigerant from
the system. If discharge pressure is low, add
refrigerant to the system.
S Add or remove charge in increments.
S Allow the system to stabilize each time
refrigerant is added or removed.
6- Use one of the following charge verification methods
along with the normal operating pressures to confirm
readings.
Charge Verification - Approach Method - AHRI Testing
1- Using the same thermometer, compare liquid
temperature to outdoor ambient temperature.
Approach Temperature = Liquid temperature (at
condenser outlet) minus ambient temperature.
2- Approach temperature should be 3.8
0.5). An approach temperature greater than this
value indicates an under-charge. An approach
temperature less than this value indicates an
overcharge.
3- The approach method is not valid for grossly over or
undercharged systems. Use table 1 as a guide for
typical operating pressures.
LHT/LDT024, 036, 048, 060
F + 1 (2.1
C +
Unit
024
036
048
060
Page 25
TABLE 5
581065-01
024 NORMAL OPERATING PRESSURES
Outdoor Coil
Entering Air Temp
655 F
755 F
855 F
955 F
1055 F
1155 F
TABLE 6
581066-01
036 NORMAL OPERATING PRESSURES
Outdoor Coil
Discharge
Entering Air Temp
655 F
755 F
855 F
955 F
1055 F
1155 F
TABLE 7
581067-01
048 NORMAL OPERATING PRESSURES
Outdoor Coil
Discharge
Entering Air Temp
655 F
755 F
855 F
955 F
1055 F
1155 F
TABLE 8
581068-01
060 NORMAL OPERATING PRESSURES
Outdoor Coil
Discharge
Entering Air Temp
655 F
755 F
855 F
955 F
1055 F
1155 F
TABLE 9
SUBCOOLING TEMPERATURE
Liquid Saturated Temp. Minus
Liquid Temperature
7.4°F + 1 (4.1°C + 0.5)
7.6°F + 1 (4.2°C + 0.5)
5.7°F + 1 (3.2°C + 0.5)
6.8°F + 1 (3.8°C + 0.5)
Discharge
Suction +
+10 psig
5 psig
242
145
281
145
325
148
377
149
415
150
472
151
Suction + 5
+10 psig
psig
259
144
301
147
347
149
390
152
448
155
511
157
Suction + 5
+10 psig
psig
247
129
284
134
328
137
375
140
425
143
480
144
Suction + 5
+10 psig
psig
259
139
299
140
343
141
391
143
444
146
506
148