Lennox LHT/LDT024 Installation Instructions Manual page 15

Table of Contents

Advertisement

Parameter
Note: Any changes to Smoke CFM setting must be adjusted before the other CFM settings. Use SETTINGS > RTU OPTIONS > EDIT
PARAMETERS = 12 for EBM, 6 for ECM
BLOWER SMOKE CFM
SETUP > TEST & BALANCE > BLOWER
BLOWER HEATING HIGH CFM
BLOWER HEATING LOW CFM
BLOWER COOLING HIGH CFM
BLOWER COOLING LOW CFM
BLOWER VENTILATION CFM
SETUP > TEST & BALANCE > DAMPER
BLOWER HIGH CFM DAMPER POS %
BLOWER LOW CFM DAMPER POS %
POWER EXHAUST DAMPER POS %
SETTINGS > RTU OPTIONS > EDIT PARAMETERS = 216
POWER EXHAUST DEADBAND %
SETTINGS > RTU OPTIONS > EDIT PARAMETERS = 10 (Applies to Thermostat Mode ONLY)
FREE COOLING STAGE-UP DELAY
Installer: Record any parameter changes under "Field Setting" column. Settings need to be recorded by installer for use when Unit Controller is replaced or
reprogrammed.
LHT/LDT024, 036, 048, 060
TABLE 4
DIRECT DRIVE PARAMETER SETTINGS - 581102-01
024-072 Parameter Settings
Field Setting
Percentage of torque for blower smoke speed.
%
%
Percentage of torque for blower heating high speed.
%
Percentage of torque for blower heating low speed (P volt gas heat only).
%
Percentage of torque for blower cooling high speed.
Percentage of torque for blower cooling low speed and vent speed for standard
%
static blowers.
%
Percentage of torque for high static blower ventilation speed.
Minimum damper position for high speed blower operation. Default 0%.
%
Minimum damper position for low speed blower operation. Default 0%.
%
Minimum damper position for low power exhaust operation. Default 50%.
%
Deadband % for power exhaust operation. Default 10%.
%
Number of seconds to hold blower at low speed before switching to blower at high
sec
speed. Default 300 seconds.
Page 15