Address Space - Siemens SIMATIC S7-1500 Equipment Manual

Digital output module dq 16x230vac/1a sttriac
Hide thumbs Also See for SIMATIC S7-1500:
Table of Contents

Advertisement

4.3

Address space

The module can be configured differently in STEP 7; see following table. Depending on the
configuration, additional/different addresses are assigned in the process image output/input.
Configuration options of DQ 16x230VAC/1A ST
You can configure the module with STEP 7 or with a GSD file.
When you configure the module by means of the GSD file, the configurations are available
under different short designations/module names.
The following configurations are possible:
Table 4- 2
Configuration options
Configuration
1 x 16-channel without value status
2 x 8-channel without value status
1 x 16-channel with value status for
module-internal Shared Output with up
to 4 submodules
Value status (Quality Information, QI)
The value status is always activated for the DQ 16x230VAC/1A ST MSO.
An additional bit is assigned to each channel for the value status. The bit for the value status
indicates if the output value specified by the user program is actually pending at the module
terminal (0 = value is incorrect).
Digital output module DQ 16x230VAC/1A ST Triac (6ES7522-5FH00-0AB0)
Equipment Manual, 12/2021, A5E34934069-AC
Short designation/module
name in the GSD file
DQ 16x230VAC/1A ST
DQ 16x230VAC/1A ST S
DQ 16x230VAC/1A ST MSO
Parameters/address space
Configuration software, e.g., STEP 7
Integrated in hard-
ware catalog STEP 7
STEP 7 V12 or higher or
V13, SP1 or higher
STEP 7 V5.5 SP3 or high-
with HSP 0119
X
X
(PROFINET IO only)
X
(PROFINET IO only)