Communication Cable Connections; Data Allocation - M-system R7C-DA16 Instruction Manual

Discrete input module, 16 points
Table of Contents

Advertisement

COMMUNICATION CABLE CONNECTIONS

Master Unit
TERMINATOR
blue
DA
white
DB
yellow
DG
SLD
FG
Be sure to connect the terminating resistor included in the product package to the unit at both ends of communication line.
The terminator must be connected across DA and DB.
The Master Unit can be located other than at the extreme ends of communication line.

DATA ALLOCATION

R7C-DA16
Interval-timed Response (X)
0
RX(n+0)F to RX(n+0)0
F
Unused
1F
R7C-DA16 + R7C-EA16
Interval-timed Response (X)
0
RX(n+0)F to RX(n+0)0
F
RX(n+1)F to RX(n+1)0
1F
R7C-DA16 + R7C-EC16x
Interval-timed Response (X)
0
RX(n+0)F to RX(n+0)0
F
Unused
1F
I/O DATA DESCRIPTIONS
DISCRETE I/O
15
0 : OFF
1 : ON
SEN TRONIC
Remote Unit
DA
DB
DG
SLD
FG
(R7C-DA16)
(R7C-DA16)
(R7C-EA16)
(R7C-DA16)
0
Input 0 (Output 0)
Input 1 (Output 1)
Input 2 (Output 2)
Input 3 (Output 3)
:
Input 7 (Output 7)
Input 8 (Output 8)
:
Input 15 (Output 15)
056 222 38 18
mailbox@sentronic.com
AG
Remote Unit
TERMINATOR
DA
DB
DG
SLD
FG
Refresh Data (Y)
0
F
Unused
1F
Refresh Data (Y)
0
F
Unused
1F
Refresh Data (Y)
0
Unused
F
RY(n+1)F to RY(n+1)0
1F
8 points
:
16 points
:
www.sentronic.com
R7C-DA16
(R7C-EC16x)
EM-7801-F Rev.6 P. 5 / 9