Endress+Hauser Waterpilot FMX21 Operating Instructions Manual
Endress+Hauser Waterpilot FMX21 Operating Instructions Manual

Endress+Hauser Waterpilot FMX21 Operating Instructions Manual

Hydrostatic level measurement
Table of Contents

Advertisement

BA00380P/00/EN/15.15
71293257
Valid as of version
01.00.zz
Products

Operating Instructions

Waterpilot FMX21
Hydrostatic level measurement
HART
Solutions
Services

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the Waterpilot FMX21 and is the answer not in the manual?

Questions and answers

Summary of Contents for Endress+Hauser Waterpilot FMX21

  • Page 1: Operating Instructions

    Products Solutions Services BA00380P/00/EN/15.15 71293257 Valid as of version 01.00.zz Operating Instructions Waterpilot FMX21 Hydrostatic level measurement HART...
  • Page 2 • The manufacturer reserves the right to modify technical data without prior notice. Your Endress+Hauser distributor will supply you with current information and updates to these Instructions. Endress+Hauser...
  • Page 3: Table Of Contents

    12.4 Disposal ......Post-connection check ....31 Endress+Hauser...
  • Page 4 16.6 Additional technical data ....131 Index ....... . . 132 Endress+Hauser...
  • Page 5: Document Information

    This other connections. may be a potential equalization line or a star grounding system depending on national or company codes of practice. 1.2.3 Tool symbols Symbol Meaning Flat blade screwdriver A0011220 Philips screwdriver A0011219 Endress+Hauser...
  • Page 6: Documentation

    Views A-A, B-B, C-C, ... Sections Documentation The document types listed are available: In the Downloads area of the Endress+Hauser website: www.endress.com → Downloads 1.3.1 Technical Information (TI): planning aid for your device TI00431P: The document contains all the technical data on the device and provides an overview of the accessories and other products that can be ordered for the device.
  • Page 7: Terms And Abbreviations

    The nameplate indicates the Safety Instructions (XA) that are relevant to the device. Terms and abbreviations Term/abbreviation Explanation Document type "Safety Instructions" Document type "Brief Operating Instructions" Document type "Operating Instructions" Document type "Special Documentation" Turn down Set span and zero-based span. Endress+Hauser...
  • Page 8: Basic Safety Instructions

    2.2.1 Application and media The Waterpilot FMX21 is a hydrostatic pressure sensor for measuring the level of fresh water, wastewater and salt water. The temperature is measured simultaneously in the case of sensor versions with a Pt100 resistance thermometer. An optional temperature head transmitter converts the Pt100 signal to a 4 to 20 mA signal with superimposed digital communication protocol HART 6.0.
  • Page 9: Product Safety

    It meets general safety standards and legal requirements. It also complies with the EC directives listed in the device-specific EC Declaration of Conformity. Endress+Hauser confirms this by affixing the CE mark to the device.
  • Page 10: Product Description

    The ceramic measuring cell is a dry measuring cell i.e. the pressure acts directly on the robust, ceramic process isolating diaphragm of the Waterpilot FMX21. Potential changes in air pressure are guided via a pressure compensation tube through the extension cable to the rear of the ceramic process isolating diaphragm and are compensated for.
  • Page 11: Incoming Acceptance And Product

    Is the order code on the delivery note (1) identical to the order code on the product sticker (2)? A0026535 A0015502 A0026536 Are the goods undamaged? A0015502 DELIVERY NOTE Made in Germany, D-79689 Maulburg Waterpilot FMX21 Order code: Ser. no.: Ext. order code: TAG: Cal./Adj. Mat: FW.Ver.: Dev.Rev.: Dat./Insp.:...
  • Page 12: Product Identification

    Is the documentation available? If required (see nameplate): Are the safety instructions (XA) present? If one of these conditions does not apply, please contact your Endress+Hauser sales office. Product identification The following options are available for identification of the measuring device: •...
  • Page 13: Nameplates

    Waterpilot FMX21 Incoming acceptance and product identification Nameplates 4.3.1 Nameplates on extension cable Made in Germany, D-79689 Maulburg Waterpilot FMX21 Order code: Ser. no.: Ext. order code: TAG: Cal./Adj. Mat: FW.Ver.: Dev.Rev.: Dat./Insp.: A0018802 Order code (shortened for reordering); The meaning of the individual letters and digits is explained in the order confirmation details.
  • Page 14: Identification Of Sensor Type

    Transport measuring device in the original packaging. ‣ Follow the safety instructions and transport conditions for devices weighing more than 18 kg (39.6 lbs). Scope of delivery The scope of delivery comprises: • Waterpilot FMX21, optionally with integrated Pt100 resistance thermometer • Optional accessories Endress+Hauser...
  • Page 15 • The Operating Instructions BA00380P are available on the internet. → see: www.de.endress.com → Downloads. • Brief Operating Instructions KA01189P • Final inspection report • Drinking water approvals (optional): SD00289P, SD00319P, SD00320P • Devices that are suitable for use in hazardous areas: Additional documentation e.g. Safety Instructions (XA, ZD) Endress+Hauser...
  • Page 16: Installation

    Terminal Box for FMX21 OPEN 90° CLOSE 90° Warning: Avoid electrostatic charge in explosive atmosphere. See instructions Made in Germany, D-79689 Maulburg Waterpilot FMX21 Order code: xxxxxxxxxxxxxxxxxxxxxx Ser. no.: xxxxxxxxxxxxx 4…20 mA Ext. order code: xxxxxxxxxxxxxxxxxxxxxx black 0...600mbar TAG: xxxxxxxxxxxxxxxxx Cal./Adj.
  • Page 17: Additional Mounting Instructions

    • The cable must end in a dry room or a suitable terminal box. The terminal box from Endress+Hauser provides optimum protection from the effects of humidity and weather conditions and is suitable for outdoor installation→  118.
  • Page 18: Mounting The Waterpilot With A Mounting Clamp

    3. Hold the extension cable in position (item 1) and push the clamping jaws (item 3) back down. Tap the clamping jaws gently from above to fix them in place. Endress+Hauser...
  • Page 19: Mounting The Waterpilot With A Cable Mounting Screw

    7. Slide the cover (item 2) with sealing ring (item 3) onto the adapter (item 5) and screw tightly to the adapter. To remove the cable mounting screw, perform this sequence of steps in reverse. CAUTION Risk of injury! ‣ Use only in unpressurized vessels. Endress+Hauser...
  • Page 20: Mounting The Terminal Box

    3. Screw the temperature head transmitter into the field housing tightly. (width of screwdriver blade max. 6 mm (0.24 in)) NOTICE Avoid damage to the temperature head transmitter. ‣ Do not overtighten the mounting screw too. Endress+Hauser...
  • Page 21: Mounting The Terminal Strip For The Pt100 Passive (Without Tmt182)

    Is the device undamaged (visual inspection)? Does the device conform to the measuring point specifications? For example: • Process temperature  • Process pressure • Ambient temperature • Measuring range  Are the measuring point identification and labeling correct (visual inspection)? Endress+Hauser...
  • Page 22 Installation Waterpilot FMX21  Is the device adequately protected from precipitation and direct sunlight?  Check that all screws are firmly seated. Endress+Hauser...
  • Page 23: Electrical Connection

    FMX21 A0019441 Waterpilot FMX21 Waterpilot FMX21 with Pt100 (not for use in hazardous areas); option "NB", Product Configurator order code for "Accessories" Not for the FMX21 with external diameter of 29 mm (1.14 in) 10.5 to 30 V DC (hazardous area), 10.5 to 35 V DC 4...20 mA...
  • Page 24 Connection classification as per IEC 61010-1: • Overvoltage category 1 • Pollution level 1 6.1.4 Connection data Connection classification as per IEC 61010-1: • Overvoltage category 1 • Pollution level 1 Connection data in the hazardous area See relevant XA. Endress+Hauser...
  • Page 25: Supply Voltage

    TMT182 temperature head transmitter (optional) 11.5 to 35 V DC Cable specifications In the following cases, Endress+Hauser recommends the use of a shielded cable as the cable extension: • For large distances between the end of the extension cable and the display and/or evaluation unit •...
  • Page 26: Current Consumption

    Safety Instructions or installation or control drawings (XA) must be adhered to. • When operating via a handheld terminal or via a PC with an operating program, a minimum communication resistance of 250 Ω must be taken into account. Endress+Hauser...
  • Page 27: Connecting The Measuring Unit

    Connection for integrated Pt100 in the FMX21 4 to 20 mA HART (temperature) 4 to 20 mA HART (level) Overvoltage protection, e.g. HAW from Endress+Hauser (not for use in hazardous areas). Power supply Further information on the TMT182 temperature head transmitter for HART applications from Endress+Hauser can be found in the Technical Information TI00078R/09/EN.
  • Page 28 Do not change the battery of the handheld terminal in the hazardous area. ‣ When using the measuring device in a hazardous area, the relevant national standards and regulations as well as the Safety Instructions (XAs) or installation or control drawings (ZDs) must be adhered to. Endress+Hauser...
  • Page 29 Connecting an external temperature sensor/temperature head transmitter for density compensation The Waterpilot FMX21 can correct measured errors that result from fluctuations in the density of the water caused by temperature. Users can choose from the following options: Use the internally measured sensor temperature of the FMX21 The internally measured sensor temperature is calculated in the Waterpilot FMX21 for density compensation.
  • Page 30 Use an external temperature signal which is transmitted to the FMX21 via HART burst mode The Waterpilot FMX21 is available with an optional Pt100 temperature sensor. In this case, the signal of the Pt100 is analyzed using a HART-compliant (min. HART 5.0) temperature head transmitter that supports burst mode.
  • Page 31: Post-Connection Check

    Do the cables comply with the requirements ?  Do the cables have adequate strain relief?  Are all cable glands installed, securely tightened and leak-tight?  Does the supply voltage match the specifications on the nameplate?  Is the terminal assignment correct ? Endress+Hauser...
  • Page 32: Operation Options

    Endress+Hauser offers comprehensive measuring point solutions with display and/or evaluation units for the Waterpilot FMX21 and TMT182 temperature head transmitter. Your Endress+Hauser service organization would be glad to be of service if you have any other questions. Contact addresses can be found on the website at www.endress.com/worldwide...
  • Page 33: Operating Concept

    The "Extended setup" submenu contains additional parameters for more in-depth configuration of the measurement operation, for conversion of the measured value and for scaling the output signal. This menu is split into additional submenus depending on the measuring mode selected. Endress+Hauser...
  • Page 34: Locking/Unlocking Operation

    The release code is "0" in the order configuration. Another release code can be defined in the "Code definition" parameter. If the user has forgotten the release code, the release code can be visible by entering the number "5864". The release code is defined in the "Code definition" parameter. Code definition Endress+Hauser...
  • Page 35: Resetting To Factory Settings (Reset)

    Any customer-specific configuration carried out at the factory is not affected by a reset (customer-specific configuration remains). If you want to change the customer- specific configuration carried out at the factory, please contact Endress+Hauser Service. As there is no separate service level, the order code and serial number can be changed without a specific release code.
  • Page 36: Integrating Device Via Hart

    Operating tools Operating tool Reference sources for device descriptions (DD and DTM) FieldCare • www.endress.com → Downloads area • CD–ROM (contact Endress+Hauser) • DVD (contact Endress+Hauser) AMS Device Manager www.endress.com → Downloads area (Emerson Process Management) SIMATIC PDM www.endress.com →...
  • Page 37: Device Variables And Measured Values

    Only level HART_INPUT_VALUE HART input val. Cannot be selected as output None (no device variable is mapped) All (but only for quaternary variable) The device variables can be queried from a HART ® master using HART ® command 9 or Endress+Hauser...
  • Page 38: Commissioning

    • Function check →  38 • Selecting the language, measuring mode and pressure unit →  39 • Position adjustment →  40 • Configuring measurement: – Pressure measurement →  41 – Level measurement →  43 Endress+Hauser...
  • Page 39: Selecting The Language

    "Setup" operating menu and readjusted if necessary. Measuring mode Navigation Setup → Measuring mode Write permission Operators/Service engineers/Expert Description Select the measuring mode. The operating menu is structured differently depending on the measuring mode selected. Options • Meas. • Level Factory setting Level Endress+Hauser...
  • Page 40: For Selecting The Pressure Engineering Unit

    This means that you are assigning the value 0.0 to the pressure present. • Measured value (after pos. zero adjust) = 0.0 mbar • The current value is also corrected. Factory setting Cancel Calib. offset (absolute pressure sensor) Endress+Hauser...
  • Page 41: Configuring The Damping

    In this example, a device with a 400 mbar (6 psi) sensor module is configured for the 0 to +300 mbar (0 to 4.5 psi) measuring range i.e. 0 mbar is assigned to the 4 mA value and 300 mbar (4.5 psi) is assigned to the 20 mA value. Endress+Hauser...
  • Page 42 Due to the orientation of the device, there may be pressure shifts in the measured value, i.e. the measured value is not zero in a pressureless condition. For information on how to perform a position adjustment, see →  40. Endress+Hauser...
  • Page 43: Configuring Level Measurement

    • The values entered for "Empty calib./Full calib.", "Empty pressure/Full pressure", "Empty height/Full height" and "Set LRV/Set URV" must be at least 1% apart. The value will be rejected, and a warning message displayed, if the values are too close together. Endress+Hauser...
  • Page 44 (URV) must be checked in the "Setup" operating menu and readjusted if necessary. Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example. Menu path: Setup → Press. eng. unit r = 1 A0018818 Endress+Hauser...
  • Page 45 → Set URV If the process uses a medium other than that on which the calibration was based, the new density must be specified in the "Process density" parameter. Menu path: Setup → Extended setup → Current output → Process density. Endress+Hauser...
  • Page 46 "mbar" for example. Menu path: Setup → Press. eng. unit A0018824 See table, step 9. Select the "In pressure" level mode via the "Level See table, step 10. selection" parameter. Menu path: Setup → Extended setup → Level → Level selection. Endress+Hauser...
  • Page 47 Menu path: Setup → Extended setup → Current output → Set LRV Use the "Set URV" parameter to set the upper current value (20 mA) (3 m (9.8 ft)). Menu path: Setup → Extended setup → Current output → Set URV Endress+Hauser...
  • Page 48 (URV) must be checked in the "Setup" operating menu and readjusted if necessary. Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example. Menu path: Setup → Press. eng. unit r = 1 A0018827 Endress+Hauser...
  • Page 49 "l" (liter) for example. Menu path: Setup → Extended setup → Level → Output unit Select a level unit via the "Height unit" parameter, "m" for example. Menu path: Setup → Extended setup → Level → Height unit Endress+Hauser...
  • Page 50 (see Step 4). Result: The measuring range is configured for 0 to 1 000 l (0 to 264 gal). For this level mode, the measured variables %, level, volume and mass are available, see "Unit before lin." . Endress+Hauser...
  • Page 51 For this reason, the "Adjust density" (step 11) and "Process density" (step 14) parameters are not used here. Select a pressure unit via the "Press. eng. unit" parameter, here "mbar" for example. Menu path: Setup → Press. eng. unit Endress+Hauser...
  • Page 52 Menu path: Setup → Extended setup → Level → Process density.  The process density can only be changed if automatic density correction is switched off (see Step 4). Result: The measuring range is configured for 0 to 1 000 l (0 to 264 gal). Endress+Hauser...
  • Page 53 Set the value for "Empty calib." with the acting pressure for the level, e.g. 20 % Menu path: Setup → Extended setup → Level → Empty calib. A0018841 See table, step 2 See table, step 3 Endress+Hauser...
  • Page 54 (electrical differential pressure) Example: In this example, a Waterpilot FMX21 and a Cerabar M device (each with an absolute pressure measuring cell) are connected via the common communication bus. The level can thus be measured in a deep well, with simultaneous compensation for the effect of atmospheric pressure.
  • Page 55 Configure an address ≠0 using the "Bus address" parameter, e.g. bus address = 1. (HART 5.0 master: Range 0 to 15, where address = 0 calls up the "Signaling" setting; HART 6.0 master: Range 0 to 63) Menu path: Expert → Communication → HART config Endress+Hauser...
  • Page 56: Automatic Density Compensation

    Automatic density compensation with the internally measured sensor temperature Example: In this example, a Waterpilot FMX21 is used for level measurement in water. The change in the water density caused by changing temperatures is automatically factored into the level signal by activating the automatic density compensation.
  • Page 57 PLC), where a corrected level value can be generated using a stored linearization table or density function (of a chosen medium). A pressure signal and a temperature signal can thus be generated with a chosen density function to compensate for a level. Endress+Hauser...
  • Page 58 Pt100 is analyzed using a HART-compliant (min. HART 5.0) temperature head transmitter that supports burst mode. The change in the water density caused by changing temperatures is automatically factored into the level signal by activating the automatic density compensation. Endress+Hauser...
  • Page 59: Linearization

    The TMT182 temperature head transmitter is not suitable for this configuration. 9.12 Linearization 9.12.1 Semi-automatic entry of a linearization table Example: In this example, the volume in a tank with a conical outlet should be measured in m Endress+Hauser...
  • Page 60 To enter another point in the table, continue filling the tank and select the "Next point" option via the "Edit table" parameter. Enter the next point as explained in Step 4. Menu path: Setup → Extended setup → Linearization → Edit table A0017670 Endress+Hauser...
  • Page 61 Select the "Manual entry" option via the "Lin. mode" parameter. Menu path: Setup → Extended setup → Linearization → Lin. mode [m ] Select using the "Unit after lin." e.g. m Menu path: Setup → Extended setup → Linearization → Unit after lin. A0018843 Height Volume Endress+Hauser...
  • Page 62: Manual Entry Of A Linearization Table Via Operating Tool

    In addition, it is possible to configure different tank shapes in FieldCare ("Device operation" → "Device functions" → "Additional functions" → "Linearization table" menu). The linearization table may also be entered manually point by point in the operating tool menu (see section). Endress+Hauser...
  • Page 63: Backing Up Or Duplicating The Device Data

    DIP switch set to "SW" and "Damping" set to "on". If you download using the factory setting "Configuration copy", all parameters required for a measurement will be downloaded. The functionality of the "Electronics replace" setting is reserved for Endress+Hauser Service and can be accessed only if the correct device access code is entered.
  • Page 64: Diagnostics And Troubleshooting

    • Outside its technical specifications (e.g. during warm-up or cleaning). A0013958 • Outside the parameter configuration undertaken by the user (e.g. level outside of configured span) Diagnostic event and event text The fault can be identified by means of the diagnostic event. Endress+Hauser...
  • Page 65 • Faulty sensor. • Check the sensor module • Electromagnetic effects are greater than cable specifications in the technical data. This message • Contact Endress+Hauser appears for a short time only. Service F081 Initialization • Faulty sensor. • Check sensor cable •...
  • Page 66 • Activate table F841 Sensor range • Overpressure or low pressure present. • Check the pressure value • Faulty sensor. • Contact Endress+Hauser Service F882 Input signal External measured value is not received or displays a • Check the bus failure status.
  • Page 67: Troubleshooting Specific To Waterpilot Fmx21 With Optional Pt100

    • The calibration carried out would result in values that exceed or fall below the nominal range of the sensor. 10.3 Troubleshooting specific to Waterpilot FMX21 with optional Pt100 Error description Reason Corrective action No measuring signal 4 to 20 mA cable not connected Connect device as per.
  • Page 68: Troubleshooting Specific To Tmt182 Temperature Head Transmitter

    Pt100 connected in 2-wire circuit, cable • Compensate the cable resistance. is inaccurate/incorrect (only resistance was not compensated for • Connect Pt100 as 3-wire or 4-wire for Waterpilot FMX21 with circuit. Pt100) 10.4 Troubleshooting specific to TMT182 temperature head transmitter...
  • Page 69: Firmware History

    Waterpilot FMX21 Diagnostics and troubleshooting 10.6 Firmware history Date Firmware version Modifications Documentation 05.2009 01.00.zz Original firmware. BA00380P/00/EN/08.09 Compatible with: • FieldCare from version 2.02.00 • Field Communicator DXR375 with Device Rev.: 1, DD Rev.: 1 Endress+Hauser...
  • Page 70: Maintenance

    • The cleaning agents used should not corrode the surface and the seals. • Mechanical damage to the process isolating diaphragm, e.g. due to sharp objects, must be avoided. • Only clean the terminal box with water or with a cloth dampened with very diluted ethanol. Endress+Hauser...
  • Page 71: Repairs

    Endress+Hauser is required to follow certain procedures when handling returned products that have been in contact with a medium. To ensure swift, safe and professional device returns, please read the return procedures and conditions on the Endress+Hauser website www.services.endress.com/return-material ‣...
  • Page 72: Overview Of The Operating Menu

    →  91 Adjust density →  91 Process density →  92 Level before lin →  92 Setup → Extended setup → Linearization Description Lin. mode →  93 Unit after lin. →  93 Line-numb: →  93 Endress+Hauser...
  • Page 73 Event logbook Description Last diag. 1 →  115 Last diag. 2 →  115 Last diag. 3 →  115 Last diag. 4 →  115 Last diag. 5 →  115 Last diag. 6 →  115 Endress+Hauser...
  • Page 74 →  116 Sim. pressure →  116 Sim. level →  116 Sim. tank cont. →  117 Sim. current →  117 Sim. alarm/warning →  117 Diagnosis → Enter reset code Description Enter reset code →  83 Endress+Hauser...
  • Page 75: Overview Of Parameters In The "Expert" Menu

    →  85 Expert → Measurement→ Meas. Description Set LRV →  86 Set URV →  86 Pressure measured →  86 Sensor pressure →  86 Corrected press. →  87 Press after damping →  87 Endress+Hauser...
  • Page 76 Hi Trim Sensor →  97 Expert → Output→ Current output Description Output current →  98 Alarm behav. P →  98 Output fail mode →  98 Max. alarm curr. →  98 Set min. current →  99 Endress+Hauser...
  • Page 77 Third value is →  107 Third value →  107 4th value is →  107 4th value →  108 Expert → Communication→ HART Input Description HART input val. →  109 HART input stat. →  109 Endress+Hauser...
  • Page 78 →  115 Last diag. 5 →  115 Last diag. 6 →  115 Last diag. 7 →  115 Last diag. 8 →  115 Last diag. 9 →  115 Last diag. 10 →  115 Endress+Hauser...
  • Page 79 Overview of the operating menu Expert → Diagnosis→ Simulation Description Simulation mode →  116 Sim. pressure →  116 Sim. level →  116 Sim. tank cont. →  117 Sim. current →  117 Sim. alarm/warning →  117 Endress+Hauser...
  • Page 80: Description Of Device Parameters

    "5864". Factory setting Code definition Write permission Operators/Service engineers/Expert Description Use this function to enter a release code with which the device can be unlocked. Options A number from 0 to 9999 Factory setting Endress+Hauser...
  • Page 81: Expert → System → Instrument Info

    Enter the device tag e.g. TAG number (max. 32 alphanumeric characters). Factory setting No entry or according to order specifications Serial number Write permission Parameter is read only. Only Endress+Hauser Service has write permission. Description Displays the serial number of the device (11 alphanumeric characters). Firmware Version Write permission No write permissions.
  • Page 82 Description of device parameters Waterpilot FMX21 Order identifier Navigation Diagnosis → Instrument info → Order identifier Write permission Parameter is read only. Only Endress+Hauser Service has write permission. Description Displays the order identifier. Factory setting According to order specifications ENP version...
  • Page 83: Expert → System → Management

    "Setup" operating menu and readjusted if necessary. Write permission Operators/Service engineers/Expert Description Select the measuring mode. The operating menu is structured differently depending on the measuring mode selected. Options • Meas. • Level Factory setting Pressure or according to order specifications Endress+Hauser...
  • Page 84: Expert → Measurement → Basic Setup

    (if the "Damping" DIP switch is set to "on") Description Enter damping time (time constant t). The damping affects the speed at which the measured value reacts to changes in pressure. Input range 0.0 to 999.0 s Factory setting 2.0 sec. or according to order specifications Endress+Hauser...
  • Page 85 The setting affects the unit for the "Sensor temp." parameter. Factory setting °C Sensor temp. Write permission No write permissions. Parameter is read only. Description Displays the temperature currently measured in the sensor module. This can deviate from the process temperature. Endress+Hauser...
  • Page 86: Expert → Measurement → Pressure

    Sensor → Sensor trim → Position adjustment → Damping ↓ ↓ ↓ ↓ Sensor pressure Corrected Corrected Meas. press. Damping pressure Sensor pressure Write permission No write permissions. Parameter is read only. Description Displays the measured pressure before the sensor trim. Endress+Hauser...
  • Page 87 No write permissions. Parameter is read only. Description Displays the measured pressure after sensor trim and position adjustment. Pressure after damping Write permission No write permissions. Parameter is read only. Description Displays the measured pressure after sensor trim, position adjustment and damping. Endress+Hauser...
  • Page 88: Expert → Measurement → Level

    • New measured value: 0.3 m Options • % • mm, cm, dm, m • ft, inch • m , in • l, hl • ft • gal, Igal • kg, t • lb Factory setting Height unit Write permission Operators/Service engineers/Expert Endress+Hauser...
  • Page 89 • In the case of dry calibration, the level (vessel empty) does not have to be available. For the "In pressure" level selection, the associated pressure must be entered in the "Empty pressure" parameter. The associated height must be entered in the "Empty height" parameter for the "In height" level selection. Factory setting Empty pressure Endress+Hauser...
  • Page 90 The associated height has to be entered in the "Full height" parameter for the "In height" level selection. Factory setting 100.0 Full pressure Write permission Operators/Service engineers/Expert Description Enter the pressure value for the upper calibration point (vessel full). See also "Full calib.". Endress+Hauser...
  • Page 91 Enter the density of the medium used to perform the calibration. The measured pressure is converted to a height using the "Height unit" and "Adjust density" parameters. Input: Auto dens. corr. = Off Display: Auto dens. corr. ≠ Off Factory setting Endress+Hauser...
  • Page 92 "Adjust density" and "Process density" parameters must be entered correctly before changing the calibration mode. Factory setting Level before lin. Write permission No write permissions. Parameter is read only. Description Displays the level value prior to linearization. Endress+Hauser...
  • Page 93: Expert → Measurement → Linearization

    Select volume unit, mass, height or % (unit of the Y-value). Options • % • cm, dm, m, mm • hl • in , ft • l • in, ft • kg, t • lb • gal • Igal Factory setting Line-numb Write permission Operators/Service engineers/Expert Endress+Hauser...
  • Page 94 • Current point: Stay on the current point to correct a mistake, for example. • Last point: Skip back to the previous point to correct a mistake, for example. • Insert point: Insert an additional point (see example below). • Delete point: Delete the current point (see example below). Endress+Hauser...
  • Page 95 6th point becomes Point 5. Factory setting Current point Tank description Write permission Operators/Service engineers/Expert Description Enter tank description (max. 32 alphanumeric characters). Tank content Write permission Operators/Service engineers/Expert Description Displays the level value after linearization. Endress+Hauser...
  • Page 96: Expert → Measurement → Sensor Limits

    Expert → Measurement → Sensor limits LRL sensor Write permission No write permissions. Parameter is read only. Description Displays the lower-range limit of the sensor. URL sensor Write permission No write permissions. Parameter is read only. Description Displays the upper-range limit of the sensor. Endress+Hauser...
  • Page 97: 14.10 Expert → Measurement → Sensor Trim

    Hi sensor trim Write permission No write permissions. Parameter is read only. Description Sensor module recalibration by entering a target pressure while simultaneously and automatically accepting a reference pressure present for the upper calibration point. Endress+Hauser...
  • Page 98: 14.11 Expert → Output → Current Output

    • Hold: last measured value is held. • Min: 3.6 mA Factory setting Max (22 mA) High alarm curr. Write permission Operators/Service engineers/Expert Description Enter the current value for maximum alarm current. See also "Output fail mode". Input range 21 to 23 mA Endress+Hauser...
  • Page 99 Set the pressure value, level or content for the lower current value (4 mA). Factory setting • 0.0 % in Level measuring mode • 0.0 mbar/bar or in accordance with ordering information in Pressure measuring mode Get URV (pressure measuring mode) Write permission Operators/Service engineers/Expert Endress+Hauser...
  • Page 100 Write permission Service engineers/Expert Description Enter the pressure value for the lower point (4 mA) of the current partial regression lines. Using this parameter and "Curr. trim 20 mA", you can adapt the current output to the transmission conditions. Endress+Hauser...
  • Page 101 Display/enter the difference between 4 mA and the value entered for the parameter "Curr. trim 4mA". Factory setting Offset trim 20mA Write permission Service engineers/Expert Description Display/enter the difference between 20 mA and the value entered for the parameter "Curr. trim 20mA". Factory setting Endress+Hauser...
  • Page 102: 14.12 Expert→ Communication → Hart Config

    Service engineers/Expert Description Configure current mode for HART communication. Options • Signaling Measured value transmission by the current value • Fixed Fixed current 4.0 mA (multidrop mode) (Measured value transmission via HART digital communication only) Factory setting Signaling Bus address Endress+Hauser...
  • Page 103 Use this function to enter the number of preambles in the HART protocol. (Synchronization of the modem components along a transmission path, each modem component could "swallow" one byte, at least 2 bytes must be the preamble.) Input range 2...20 Factory setting Endress+Hauser...
  • Page 104: 14.13 Expert→ Communication → Hart Info

    Device type Write permission No write permissions. Parameter is read only. Description Display of the numerical ID of the device Waterpilot FMX21: 36 Device revision Write permission No write permissions. Parameter is read only. Description Display of device revision (e.g. 1)
  • Page 105 Enter message (max. 32 alphanumeric characters). Upon request from the master, this message is sent via the HART protocol. HART date Write permission Service engineers/Expert Description Enter the date of the last configuration change. Factory setting DD/MM/YY (date of the final test) Endress+Hauser...
  • Page 106: 14.14 Expert→ Communication → Hart Output

    Depending on the selected measuring mode, the following measured values can be displayed: • "Meas. pressure" • "Sensor pressure" • "Corrected press." • "Pressure after damping" • "Sensor temp." • "Level before Lin" • "Tank content" • "Process density" (corrected) Secondary value Endress+Hauser...
  • Page 107 • "Pressure" measuring mode: "Sensor temp" • "Level" measuring mode, "Linear" lin. mode: "Sensor temp." • "Level" measuring mode, "Activate table" lin. mode: "Sensor temp." Display Depending on the selected measuring mode, the following measured values can be displayed: Endress+Hauser...
  • Page 108 • "Sensor pressure" • "Corrected press." • "Pressure after damping" • "Sensor temp." • "Level before Lin" • "Tank content" • "Process density" (corrected) 4th value Write permission No write permissions. Parameter is read only. Description The fourth value is displayed. Endress+Hauser...
  • Page 109: 14.15 Expert→ Communication → Hart Input

    • psi • mmHg, inHg • Torr • g/cm , kg/cm • lb/ft • atm • °C, °F, K, R Factory setting Unknown HART input form. Write permission Operators/Service engineers/Expert Description Number of decimal places of the displayed input value. Endress+Hauser...
  • Page 110 Description of device parameters Waterpilot FMX21 Options • x.x • x.xx • x.xxx • x.xxxx • x.xxxxx Factory setting Endress+Hauser...
  • Page 111: 14.16 Expert → Application

    Level mode Options • Off • Sensor temperature • External value (only if Electr. Delta P option is off or constant) Factory setting • Off • On (if the option "IC" was selected in the "Service" order code when ordering) Endress+Hauser...
  • Page 112: 14.17 Expert → Diagnosis

    No write permissions. Parameter is read only. Description Displays the lowest pressure value measured (peakhold indicator). You can reset this indicator by means of the "Reset peakhold" parameter. Max. meas. press. Write permission No write permissions. Parameter is read only. Endress+Hauser...
  • Page 113 Displays the hours of operation. This parameter cannot be reset. Config. recorder Write permission Operators/Service engineers/Expert Description Displays the configuration counter. This counter is increased by one every time a parameter or group is changed. The counter counts up to 65535 and then starts again at zero. Endress+Hauser...
  • Page 114: 14.18 Expert → Diagnosis → Diagnostic List

    Diagnostic 8 (082) Diagnostic 9 (083) Diagnostic 10 (084) Navigation Diagnosis → Diagnostic list Write permission No write permissions. Parameter is read only. Description This parameter contains up to ten diagnosis messages that are currently pending, arranged in order of priority. Endress+Hauser...
  • Page 115: 14.19 Expert → Diagnosis→ Event Logbook

    This parameter contains the last 10 diagnosis messages to occur and be rectified. They can be reset using the "Reset logbook" parameter. Errors which have occurred multiple times are displayed once only. Errors may also appear multiple times if another error has occurred in the meantime. The messages are displayed in chronological order. Endress+Hauser...
  • Page 116: 14.20 Expert → Diagnosis → Simulation

    Write permission Operators/Service engineers/Expert Description Enter the simulation value. See also "Simulation mode". Prerequisite "Simulation mode" = Pressure Value at switch-on Current pressure measured value Sim. level Write permission Operators/Service engineers/Expert Description Enter the simulation value. See also "Simulation mode". Endress+Hauser...
  • Page 117 Enter the simulation value. See also "Simulation mode". Prerequisite "Simulation Mode" = Current value Value at switch-on Current current value Sim. alarm/warning Write permission Operators/Service engineers/Expert Description Enter the simulation value. See also "Simulation mode". Prerequisite "Simulation Mode" = Alarm/Warning Factory setting: 484 (Simulation active) Endress+Hauser...
  • Page 118: Accessories

    Accessories 15.1 Suspension clamp • For easy installation of the FMX21, Endress+Hauser offers a mounting clamp . • Material: 316L (1.4404) and fiber-glass reinforced PA (polyamide) • Order number: 52006151 • Ordering information: Product Configurator order code for "Accessories enclosed"...
  • Page 119: Temperature Head Transmitter Tmt182

    "NB" 15.6 Cable mounting screws Endress+Hauser offers a cable mounting screw for easy installation of the FMX21 and to seal the measuring aperture. • Order number for cable mounting screw: – 52008264 (G 1½" A) Ordering information: Product Configurator order code for "Accessories enclosed", option "PQ"...
  • Page 120: 15.10 Testing Adapter

    15.10.1 For FMX21 with external diameter of 22 mm (0.87 in) or 29 mm (1.14 in) • Endress+Hauser offers a testing adapter to ease function-testing of the level probes. • Observe the maximum pressure for compressed air hose and maximum overload for level probe →...
  • Page 121 ~25 (0.98) M14x1 A0018749 FMX21 level probe connection 2 Compressed air hose connection, internal diameter, quick coupling piece 4 mm (0.16 in) Engineering unit mm (in) 15.10.2 For FMX21 with external diameter of 42 mm (1.65 in) Order number: 71110310 Endress+Hauser...
  • Page 122: Technical Data

    These measuring ranges are not available for the special version with plastic insulation, external diameter of 29 mm (1.14 in). Absolute pressure Sensor measuring range Lowest calibratable span Vacuum resistance Option [bar (psi)] [bar (psi)] [bar (psi 2.0 (30.0) 0.2 (3.0) 4.0 (60.0) 0.4 (6.0) Endress+Hauser...
  • Page 123 These measuring ranges are not available for the special version with plastic insulation, external diameter of 29 mm (1.14 in). 16.1.3 Input signal FMX21 + Pt100 (optional) • Change in capacitance • Pt100: Change in resistance TMT182 temperature head transmitter (optional) Pt100 resistance signal, 4 wire Endress+Hauser...
  • Page 124: Output

    FMX21 and temperature head transmitter. The total resistance resulting from the resistances of the connected devices, the connecting cable and, where applicable, the resistance of the extension cable may not exceed the load resistance value. Endress+Hauser...
  • Page 125 17 (11 hex) Device type code 25 (19 hex) Device revision 01 (01 hex) - SW version 01.00.zz HART specification DD revision Device description files Information and files under: (DTM, DD) • www.endress.com • www.hartcomm.org HART load Min. 250 Ω Endress+Hauser...
  • Page 126 Measured values for PV (first device variable) are dependent on the measuring mode: • Meas. • Level • Tank content Supported functions • Burst mode • Additional transmitter status • Device locking • Alternative measuring modes • Catch variable • Long tag Endress+Hauser...
  • Page 127: Performance Characteristics

    Ordering information: Product Configurator order code for "Reference accuracy" option "D" TMT182 temperature head transmitter (optional) • ±0.2 K • With Pt100: max. ±0.9 K 16.3.3 Resolution Current output: 1 μA Reading cycle HART commands: on average 2 to 3 per second Endress+Hauser...
  • Page 128 • FMX21: < 6 s • Pt100: 20 m TMT182 temperature head transmitter (optional) 16.3.7 Response time FMX21 + Pt100 (optional) • FMX21: 400 ms (T90 time), 500 ms (T99 time) • Pt100: 160 s (T90 time), 300 s (T99 time) Endress+Hauser...
  • Page 129: Environment

    –40 to +80 °C (–40 to +176 °F) TMT182 temperature head transmitter (optional) –40 to +100 °C (–40 to +212 °F) 16.4.3 Degree of protection FMX21 + Pt100 (optional) IP68, permanently hermetically sealed at 20 bar (290 psi) (~200 m H Terminal box (optional) IP66, IP67 Endress+Hauser...
  • Page 130 16.4.6 Overvoltage protection FMX21 + Pt100 (optional) • Integrated overvoltage protection as per EN 61000-4-5 (500 V symmetrical/1000 V asymmetrical) • Overvoltage protection ≥ 1.0 kV, external if necessary TMT182 temperature head transmitter (optional) Overvoltage protection external if necessary Endress+Hauser...
  • Page 131: Process

    With external diameter of29 mm (1.14 in): 0 to +50 °C (+32 to +122 °F) The FMX21 may be operated in this temperature range. The specification can then be exceeded e.g. measuring accuracy 16.6 Additional technical data See Technical Information: Endress+Hauser...
  • Page 132: Index

    Last diag. 10 (094) ......115 Diagnostic 9 (083) ......114 Endress+Hauser...
  • Page 133 Reset Logbook ......112 Reset Peakhold ......113 Endress+Hauser...
  • Page 134 *71293257* 71293257 www.addresses.endress.com...
  • Page 135 Endress+Hauser Configurator 2016 SC United States v2 2350 Endress Place Greenwood, IN 46143 Waterpilot FMX21 Level measurement, Hydrostatic. Level probe. FMX21-AA211FGF30A Process membrane: CERAPHIRE, dry,rugged. Typ. ref. accuracy +/-0.2% 71082058 (Platinum 0.1%). :: Integrated overvoltage protection. SPK: PEK Basic model...