ETC Installation Guide
P-NSPS-D
Electrical
48 VDC DIN Rail Power Supply
Accepts 100-240 VAC, 50/60 Hz input, and provides 48 VDC to the P-NSPS-D.
Network Station Power Supply
Note:
SELV/LPS or Class 2 supply.
Accepts 48 VDC input (supplied by included 48 VDC DIN rail power supply).
Supports up to 63 Paradigm stations and sensors over LinkConnect (four
bus terminations available).
Ethernet RJ45 for connection to the Paradigm lighting network.
Wiring
48 VDC Power Supply
Input
Use copper wire only, 2.5 mm
minimum 60°C (140°F).
Output
Use the ETC-supplied 48 VDC power pigtail (blue and black wire pair)
between the 48 VDC Power Supply voltage output terminals and
the P-NSPS-D. No other connections are supported.
Network Station Power Supply
Input
Use the ETC-supplied 48 VDC power pigtail (blue and black wire pair) with
the three-position pluggable connector between the 48 VDC Power Supply
and the P-NSPS-D VDC input.
Note:
additional wire from the ground terminal to the shared ground used
for the LinkConnect data runs.
LinkConnect
Connect up to up to four LinkConnect data runs to the provided
eight-position connector. LinkConnect is a bidirectional protocol that carries
data and power over one pair of wires. ETC recommends Belden 8471 Class 2
wire (or approved equal - see the ETC cable cross database
etcconnect.com/Support/Cable-Cross-Database
is topology-free and polarity-independent; you may install the wires in any
P-NSPS-D
This product is intended for use with a Listed and marked
ETC requires the installed P-NSPS-D be grounded. Connect an
2
2
- 1 mm
(14-18 AWG), rated to withstand
Page 2 of 8
for alternatives). LinkConnect
ETC