Efcb Series Objects Table - Neptronic EFCB Series User Manual

Bacnet communication module
Table of Contents

Advertisement

EFCB Series Objects Table

The EFCB controllers use the following BACnet
®
form the BACnet
Object_Identifier for an object according to the following C-language algorithm:
object_identifier=(unsigned long)((unsigned long)type<<22)+instance
7
ID
Name
Intern.Temper.
AI.1
Extern.Temper.
AI.2
ChangeOverTemper.
AI.3
8
Intern.Humidity
AI.4
9
Extern.Humidity
AI.9
10
AnalogInput3
AI.13
11
AnalogInput4
AI.14
12
AnalogInput5
AI.15
13
AnalogInput6
AI.16
ControlTemper.
AV.1
HeatingDemand
AV.2
CoolingDemand
AV.3
FanDemand
AV.4
Intern.Temper.Offset
AV.5
Extern.Temper.Offset
AV.6
Temper.SetPointOcc
AV.7
7
ID is equal to ObjectType.Instance
8
Internal sensor is available when a compatible controller is connected with a TFLH-INT; otherwise object is always out of service.
9
External sensor is available when a compatible controller is connected with a TFLH-EXT or a TFLH-INT; otherwise object is always out of service.
10
This input could be analog 0-10V or thermistor mode, selectable by hardware dipswitch.
11
This input could be analog 0-10V or thermistor mode, selectable by hardware dipswitch.
12
This input could be analog 0-10V or thermistor mode, selectable by hardware dipswitch.
13
This input could be analog 0-10V or thermistor mode, selectable by hardware dipswitch.
®
object table. The type is the BACnet
Description
Internal temperature sensor value
External temperature sensor value
Changeover temperature sensor value
Internal humidity sensor value
External humidity sensor value
Analog input 3, mode selected by dipswitch on
EFCB
Analog input 4, mode selected by dipswitch on
EFCB
Analog input 5, mode selected by dipswitch on
EFCB
Analog input 6, mode selected by dipswitch on
EFCB
Temperature reading
Heating demand
Cooling demand
Fan demand
Internal temperature offset calibration
External temperature offset calibration
Temperature set point
®
Object type, the instance is the BACnet
Writable
Property
Out of service
x
x
x
x
x
x
Out of service
x
x
x
x
x
x
Out of service
x
x
x
x
x
x
Out of service
x
x
x
x
x
Out of service
x
x
x
x
x
Out of service
x
x
x
x
x
x
Out of service
x
x
x
x
x
x
Out of service
x
x
x
x
x
x
Out of service
x
x
x
x
x
x
Out of service
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
Present Value
x
x
x
x
x
x
Present Value
x
x
x
x
x
x
Present Value
x
x
x
x
x
x
EFCB Series Controller
®
Object. Together the type and instance
Notes
x 0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
x
x
x
x 0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
x
x
x
x 0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
x
x
x
x 5-95%RH, Resolution 0.1%RH
x
x
x
x 5-95%RH, Resolution 0.1%RH
x
x
x
If BV.6 is set to "Intern.Sensor" and/or MSV.4 = "10k"
0-10Volt or -40-100ºC or -40-212ºF, Resolution
0.01Volt or 0.01ºC/0.02ºF
x
x
x
x
If BV.6 is set to "Extern.Sensor" and MSV.4 ≠ "10k"
AV.99 to AV.100, Resolution 0.01ºC/0.02ºF
0-10Volt or -40-100ºC or -40-212ºF, Resolution
x
x
x
x
0.01Volt or 0.01ºC/0.02ºF
0-10Volt or -40-100ºC or -40-212ºF, Resolution
x
x
x
x
0.01Volt or 0.01ºC/0.02ºF
0-10Volt or -40-100ºC or -40-212ºF, Resolution
x
x
x
x
0.01Volt or 0.01ºC/0.02ºF
x 0-50ºC or 32-122ºF, Resolution 0.01ºC/0.02ºF
x
x
x
x 0-100%, Resolution 0.1%
x
x
x
x 0-100%, Resolution 0.1%
x
x
x
x 0-100%, Resolution 0.1%
x
x
x
x ±5.0ºC, Resolution 0.1ºC
x
x
x
x ±5.0ºC, Resolution 0.1ºC
x
x
x
x AV.8 to AV.9, Resolution 0.5ºC/1ºF
x
x
x
Page | 7