Object Types Supported

A complete list of all BACnet
The Device Object has already been described. The following tables list all the BACnet
for each object type. Most of the properties are locked in. The exception is Present_Value, which represents the
dynamic operating values of the device, and the Status_Flag, Event_State and Reliability properties which
reflect the availability of the Present_Value. Unless otherwise specified, properties are not changeable.
Object Type
Supported
Analog Input
Analog Value
Binary Input
Binary Value
Device
5
Multi-State Value

Out of Service

Neptronic controllers offer the use of the "Out of Service" writable property. When set to true, this property
disconnects the object from the physical input, enabling you to input other values. This could be useful for
special applications or when troubleshooting. For example, you can ignore the temperature read from a sensor
and input the desired temperature value in order to perform specific tests.
For security reasons there is a timeout that will set the Out of Service property back to false after 15 minutes.
This value can be modified to between 0 and 120 minutes (see proprietary property #1002).
1
Present_Value property is writable for every AV object except: AV.1, AV.2, AV.3, AV.42, AV.46, AV.49, AV.68, AV.69, AV.98
2
Out_of_Service property is writable for objects that Present_Value is not writable: AV.1, AV.68, AV.69. Object will automatically return to
normal after a programmable period of time. See Proprietary property #1002 of Device object.
3
Present_Value property is writable for every BV object except: BV.7, BV26, BV27, BV28, BV36, BV37
4
Out_of_Service property is writable for objects that Present_Value is not writable. See list above. Object will automatically return to normal
after a programmable period of time. See Proprietary property #1002 of Device object.
5
MSV object states number and text can vary depending of system set-up. Use carefully.
6
Present_Value property is writable for every MSV object except: MSV.9, MSV.14
®
objects for the controller is listed in the following section:
Optional Properties
Supported
Reliability
Description
Min_Present_Value
Max_Present_Value
Resolution
Reliability
Description
Reliability
Active_Text
Inactive_Text
Description
Reliability
Active_Text
Inactive_Text
Description
Max_Master
Max_Info_Frame
Description
#1001 (BAUD RATE)
#1002 (TIME OUT)
Description
Reliability
States_Text
Writable
If "Out of Service"
Properties
is True
Present_Value
Out_of_Service
Status_Flag
1
Present_Value
Present_Value
2
Status_Flag
Out_of_Service
Present_Value
Out_of_Service
Status_Flag
3
Present_Value
Present_Value
4
Out_of_Service
Status_Flag
Object_Identifier
Object_Name
Max_Master
N/A
Description
#1001
#1002
6
Present_Value
N/A
EFCB Series Controller
®
properties supported
Page | 6