Device Object Properties - Neptronic EFCB Series User Manual

Bacnet communication module
Table of Contents

Advertisement

Device Object Properties

The following table lists all the BACnet
property is writable using the BACnet
Property
Object_Identifier
Object_Name
Description
Object_Type
System_Status
Vendor_Identifier
Vendor_Name
Model_Name
Firmware_Revision
Application_Software_Version
Protocol_Version
Protocol_Revision
DataBase_Revision
Max_APDU_Length_Accepted
Segmentation_Supported
APDU_Timeout
Number_of_APDU_Retries
Protocol_Services_Supported
Protocol_Object_Types_Supported
Object_List
Device_Address_Binding
Max_Master
Max_Info_Frames
Proprietary property #1000
Proprietary property #1001
Proprietary property #1002
®
properties supported for the device object. The "W" indicates if the
®
WriteProperty service.
Value
Programmable where the instance part of the Object_Identifier is in
the range of 0-4194302. The device instance must be unique system-
wide. The default value for the device instance=153000
(Vendor_Identifier*1000)
Programmable up to 32 characters. The device name must be unique
system-wide. The default value is Model_Name.
Programmable up to 32 characters. The default value= "BACnet
fancoil controller"
8
Non-Operational if major error on device.
Always 153
Always "National Environmental Products Ltd"
Example : "EFCB"
currently "1.28"
currently "1.11"
Always 1
Always 4
Default = 0, will be incremented if Object_Name and/or
Odject_Identifier is modified
Always 480
(3) = No Segmentation
3000
Always 0
Always 0x00, 0x0B, 0xC0, 0x02, 0x60
(i.e. a bitstring in BACnet® order)
- writeProperty, readProperty
- writePropertyMultiple, readPropertyMultiple
- deviceCommunicationControl
- unconfirmedPrivateTransfer
- who-Is, who-Has
Always 0x00, 0xB4, 0x80, 0x10
®
(i.e. a bitstring in BACnet
order)
- analog-input, analog-value, binary-input, binary-value
- device
- multi-state-value
Per the standard. Because of restrictions on the size of the transmit
buffers, the entire Object_List cannot be returned at once, rather the
Object_List must be read, one-at-a-time.
Always empty.
Programmable in the range of 0-127. Default value=127
Always 1
Read only. This proprietary property represents the MS/TP MAC
address in the range of (0-254). Values 128 to 254 represent MS/TP
non-token-passing slave devices. Default value=0
Programmable. This proprietary property represents the MS/TP baud
rate. This value is Unsigned type, and available values are 9600,
19200, 38400, 76800. Writing 0 will activate auto baud rate
functionality. Reading this property will always return actual baud rate.
Default : Auto* (Auto Baud Rate Detection requires V1.28 and up)
Programmable. This proprietary property represents that period of
time that an object in/out of service will automatically return to normal.
Range = 0-120 minutes (unsigned type). Writing 0 means no
automatic return to normal. Default: 15 minutes.
EFCB Series Controller
Writable
W
W
W
W
W
W
Page | 5