E2S D2xB1LD3DC024 Instruction Manual

Led beacons (visual fire alarm) for use in hazardous locations
Hide thumbs Also See for D2xB1LD3DC024:

Advertisement

Quick Links

1) Warnings
 DO NOT OPEN WHEN AN EXPLOSIVE
ATMOSPHERE IS PRESENT
 DO NOT OPEN WHEN ENERGISED
 POTENTIAL ELECTROSTATIC CHARGING
HAZARD - CLEAN ONLY WITH A DAMP
CLOTH
 DO NOT PAINT
Avertissement:
 NE PAS OUVRIR UN PRESENCE
D'ATMOSPHERE EXPLOSIVE
 NE PAS OUVRIR ENERGIE
 DANGER POTENTIEL CHARGE
ÉLECTROSTATIQUE - NETTOYER
UNIQUEMENT AVEC UN CHIFFON HUMIDE
 NE PAS PENINTURER
2) Rating & Marking Information
2.1 Public Mode Fire Alarm Ratings
The D2xB1LD3DC024 is certified for use as a public mode
visual alarm device in accordance with UL1971 Third Edition
and UL1638 Fifth Edition / CAN/ULC-S526 Fourth Edition.
For light output ratings see section 12.
For use in public-mode fire alarm systems the beacon must
be installed without the wire guard or plastic lens cover.
Testing of synchronization requirements of UL1971 &
UL1638 / CAN/ULC-S526 were conducted by UL using a total
of 6 units connected to the same wire run. Auto-
synchronization does not require the use of any external sync
modules or protocols. Providing the correct cable has been
selected (see section 6) an unlimited number of units will
remain synchronized when powered from the same source.
2.2 Private Mode Fire Alarm Ratings
All models are approved for use as a Visual Appliance for use
in Private Mode Fire Alarm Systems in accordance with
UL1638 Fifth Edition / CAN/ULC-S526 Fourth Edition.
_______________________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D211-00-471-IS-SC
D2xB1LD3 LED Beacons (Visual Fire Alarm)
For use in Hazardous Locations
Issue A
27-11-19
INSTRUCTION MANUAL
For use in private-mode fire alarm systems the beacon must
be installed without the wire guard or plastic lens cover.
For light output ratings see section 12.
2.3 NEC & CEC Class / Division Ratings for US / Canada
The D2xB1LD3 LED beacon complies with the following
standards:
UL1971 Ed. 3 2018
UL1638 Ed. 5 2017 / CAN/ULC-S526 Ed. 4
CSA C22.2 No. 205-17
ANSI/ISA 12.12.01-2015
CSA C22.2 No. 213-16
The D2xB1LD3 LED beacon is rated as follows:
Class I Div 2 ABCD T4 Ta -40°C to +50°C
Class II Div 2 FG T6 Ta -40°C to +50°C
Class III Div 1&2 Ta -40°C to +50°C
The certification approval has validated continuous use up to
38°C and are for transient use up to 50°C ambient.
Installation must be carried out in compliance with the
National Electric Code / Canadian Electric Code
2.4 NEC Class / Zone ratings US
The D2xB1LD3 LED beacon complies with the following
standards:
UL 60079-0-2017
UL 60079-15-2017
UL 60079-31-2015
The D2xB1LD3 LED beacon is rated as follows:
Class I Zone 2 AEx nA IIC Gc T4 Ta -40°C to +50°C
AEx tc IIIC 75°C Dc Ta -40°C to +50°C
Installation must be carried out in compliance with the
National Electric Code.
2.5 CEC Class / Zone ratings Canada
The D2xB1LD3 LED beacon complies with the following
standards:
CAN/CSA C22.2 No. 60079-0:2015
CAN/CSA C22.2 No. 60079-15:2016
CAN/CSA C22.2 No. 60079-31:2015
The D2xB1LD3 LED beacon is rated as follows:
Ex nA IIC Gc X T4 Ta -40°C to +50°C
Ex tc IIIC 75°C Dc X Ta -40°C to +50°C
Installation must be carried out in compliance with the
Canadian Electric Code
sales@e2s.com
www.e2s.com
Sheet 1 of 8
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200

Advertisement

Table of Contents
loading

Summary of Contents for E2S D2xB1LD3DC024

  • Page 1 AEx tc IIIC 75°C Dc Ta -40°C to +50°C 2.1 Public Mode Fire Alarm Ratings Installation must be carried out in compliance with the The D2xB1LD3DC024 is certified for use as a public mode National Electric Code. visual alarm device in accordance with UL1971 Third Edition and UL1638 Fifth Edition / CAN/ULC-S526 Fourth Edition.
  • Page 2: Special Conditions Of Use

    EN60079-10-2 / IEC60079-10-2: Explosive atmospheres – Classification of areas. Explosive dust atmospheres _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D211-00-471-IS-SC...
  • Page 3: Location And Mounting

    Carefully push the cover in place. Insert M4 screws with fibre washers and tighten to 3Nm torque. _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No.
  • Page 4: Cable Connections

    Minimum Power 0.5W Minimum resistance 1K Ohms Minimum Power 2.0W _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D211-00-471-IS-SC Issue A...
  • Page 5: Maintenance, Overhaul & Repair

    Table 1: Switch Positions for Flash Patterns Fig. 8 Dip Switch (Example shown: 01 = Flashing 1.33Hz) _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com Fax: +44 (0)208 740 4200 Document No. D211-00-471-IS-SC...
  • Page 6 12) Light output for Fire alarm use In order to meet the requirements for UL1971, (D2xB1LD3DC024 only when used without plastic lens cover or wire guard), the installation must be carried out to the correct NFPA standards and guidelines. Horizontal Light Output Dispersion for wall mounting – public mode 12.1...
  • Page 7 All light output ratings min. values as per UL 1971 / UL1638 / CAN/ULC-S526 at worst-case (min.) input voltage. On-axis light output rating – private mode 12.3 Model Accessories Intensity (cd) @ 1Hz D2xB1LD3DC024 No Guard, No Lens 112.5 _______________________________________________________________________________________________________________________________ European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH sales@e2s.com Tel: +44 (0)208 743 8880 www.e2s.com...
  • Page 8: Electrical Ratings

    Range current current 1Hz (60fpm) 153mA 465mA 1.33Hz (80fpm) 189mA 488mA Regulated D2xB1LD3DC024 24Vdc (16-33Vdc)* 1.5 Hz (90fpm) 203mA 456mA 2Hz (120fpm) 248mA 528mA * For Public Mode or private mode Fire Alarm use # nominal rms current at nominal voltage ## max.