Item
Installation
The equivalent distance between the indoor unit and standard condenser is 30m;
position
Ambient
Normal temperature type: -20℃~+45℃; fluorine pump type: -40℃~+45℃
temperature
Operating
power
Altitude
Protection
Note:
"*": The condenser has a positive drop above the indoor unit, and a negative drop below it
 Note
1. When the equivalent distance between the indoor unit and standard condenser is within
30m, please refer to the specific requirements for the equivalent length of the refrigerant
connecting pipe in the Precision Air Conditioner User Manual.
2. When the equivalent distance between the indoor unit and the standard condenser exceeds
30m, please consult Shenzhen Kstar Science & Technology Co., Ltd. for details.
Chapter 1 Product Overview
Table 1-3 Operating Environment Requirements
Requirements
height difference *ΔH: -5m≤ΔH≤10m;
380V± 10%,50/60Hz
≤1000m; derated for use above 1000m.
4
IP55