2.2.2 Installation Space

There should be sufficient space for installation and maintenance around the
installation location of the KC air-cooled centralized condenser.
 Space requirements
1. The KC air-cooled centralized condenser requires at least 800mm
maintenance space at the front, rear, left, and right side.
2. There is no obstruction within at least 3000mm of the air outlet of the KC
air-cooled centralized condenser.
3. The air outlet of the KC air-cooled centralized condenser should avoid short
circuit of hot air, which will result in poor heat exchange effect, as shown in
Fig. 2-5.
The specific requirements are shown in the figure below.
Fig. 2-1 KC*032~096 Schematic diagram of dispersion distribution
Chapter 2 Installation of Condenser
8