Fig.2-9 KC*108~170 Side-by-side mounting base bracket dimensions
2.2.4 Pipeline Connection of Indoor and Outdoor Units
See Precision Air Conditioning User Manual.
2.2.5 Cable Connection of Indoor and Outdoor Units
2.2.5.1. Determine the cable specifications
Select the power supply cable and signal cable specifications according to the
rated operating current of the fan (see Table 2-1) and installation distance.
Table 2-3 Recommended cable diameter of KC air-cooled centralized condenser
Condenser model
KCS032,KCS036,KCS042,KCS048,
KCS054,KCD054
KCS064,KCD064,KCS072,KCD072,
KCS084,KCD084,KCS096,KCD096
KCS108,KCD108
KCS128,KCD128,KCS150,KCD150,
KCS170,KCD170
Note
The outdoor part of the cable between the indoor unit and the KC air-cooled centralized
condenser must use a cable suitable for outdoor use, and the signal cable must use a twisted pair
shielded cable.
Chapter 2 Installation of Condenser
h1
h
Number of
Full load
fans (PCS)
current (A)
1
1
2
2
13
Recommended
specifications
for power
supply cables
2
(mm
)
2.5
1.5*4
5.0
1.5*4
5.0
2.5*4
10.5
2.5*4
Recommended
specifications
for signal
2
cables (mm
)
0.5*2
0.5*2
0.5*2
0.5*2