Check point 6. Check strainer
•
Strainer normally does not have temperature difference between inlet and outlet as shown be-
low.
•
If there is a difference like shown below, there is a possibility of inside clogged. In this case,
replace the strainer.
4-3. Outdoor unit Electronic Expansion Valve (EEV)
Pipe (In)
Pipe (In)
- (03-45) -
Pipe (Out)
Pipe (Out)
4. Service parts information