E: 71. Discharge Thermistor Error (Outdoor Unit) - Fujitsu General ARXG45KHTB Service Manual

Duct type
Table of Contents

Advertisement

2-13. E: 71. Discharge thermistor error (Outdoor unit)

Wired remote
Indicator
controller
Outdoor unit main PCB
Detective actuator
Discharge pipe temperature
thermistor
Forecast of cause
Check point 1. Check connection of connector
Check if connector is loose or removed.
Check erroneous connection.
Check if thermistor cable is open
→ Reset power when reinstalling due to removed connector or incorrect wiring.
Check point 2. Remove connector and check thermistor resistance value
For the discharge temperature thermistor resistance value, refer to
resistance values"
If thermistor is either open or shorted, replace it and reset the power.
Check point 3. Check voltage of main PCB
Make sure circuit diagram of outdoor unit and check terminal voltage at thermistor
(DC 5.0 V).
NOTE: For details of thermistor connector, refer to
TECHNICAL DATA AND PARTS LIST on page 02-15.
If the voltage does not appear, replace main PCB.
2-13. E: 71. Discharge thermistor error (Outdoor unit)
Error code
on page 03-52.
End
- (03-19) -
When discharge pipe temperature thermistor open or
short circuit is detected at power on or while running the
compressor
Connector failure
Thermistor failure
Main PCB failure
"Thermistor
"Wiring diagrams"
in Chapter 2.
E: 71
2. Troubleshooting with error code