2) Room temperature control for indoor unit sensor
NOTE: If the remote sensor unit option is selected, perform this setting.
Depending on the installed environment, correction of the room temperature sensor may be re-
quired. Select the appropriate control setting according to the installed environment.
The temperature of the room temperature sensor is corrected as follows:
Corrected temp. = Temp. of the room temp. sensor - Correction temp. value
Example of correction:
When the temperature of the room temp. sensor is 26°C and the setting value is "03"
(-1.0°C), corrected temp. will be 27°C (26°C - [-1.0°C]).
The temperature correction values show the difference from the Standard setting "00" (manufactur-
er's recommended value).
Function number
30
(For cooling)
1-2. Function settings by using remote controller
Setting value
00
01
02
03
04
05
06
07
08
31
(For heating)
09
10
11
12
13
14
15
16
17
Setting description
Standard setting
No correction 0.0 °C
-0.5 °C
-1.0 °C
-1.5 °C
-2.0 °C
-2.5 °C
-3.0 °C
-3.5 °C
-4.0 °C
+0.5 °C
+1.0 °C
+1.5 °C
+2.0 °C
+2.5 °C
+3.0 °C
+3.5 °C
+4.0 °C
- (05-3) -
Factory
setting
More cooling
Less heating
Less cooling
More heating
1. Function settings (For indoor unit)