1-2. Heating operation
A sensor (room temperature thermistor) built in indoor unit body will usually perceive difference or
variation between setting temperature and present room temperature, and controls operation rota-
tion number of compressor.
• If the room temperature is 6.0°C lower than a set temperature, the operation rotation number of
compressor will attain to maximum performance.
• If the room temperature is 1.0°C higher than a set temperature, the compressor will be stopped.
• When the room temperature is within the range of +1.0°C to -6.0°C of the setting temperature, the
rotation number of compressor is controlled within the range shown below.
• Rotation number range of compressor
Model name
ASHH30KMTB
ASHH36KMTB
1-3. Dry operation
The rotation number of compressor shall change according to the temperature, set temperature, and
room temperature variation which the room temperature sensor of the indoor unit has detected as
shown in the table below.
Zone is defined by set temperature and room temperature.
• Rotation number range of compressor
Model name
ASHH30KMTB
ASHH36KMTB
• Compressor control based on room temperature
1-2. Heating operation
Minimum frequency
Outdoor temperature zone
Room temperature drops
X zone
Ts+0.5°C
J zone
Ts
-1.5°C
Y zone
15
X zone
J zone
Y zone
Room temperature rises
Ts: Set temperature
- (04-2) -
Unit: rps
Maximum frequency
120
Unit: rps
Operating frequency
40
17
0
Ts+1.5°C
Ts-0.5°C
1. Rotation number control of compressor