 Outputs
PLC
TYPICAL WIRING
TYPE
PLC Outputs
FX
-MT-ESS/UL
2C
1
3
FX
-MT-DSS
Source
2NC
0
2
COM
FX
-EYT-DSS
2NC
LED
Lamp
PLC Outputs
FX
-MT-E/UL
2C
1
3
FX
-MT-D/UL
Sink
2NC
0
2
COM
FX
-EYT-D/UL
2NC
Lamp
LED
For the I/O specifications and detailed information, refer to the FX
ware Manual.
7. AC INPUT BLOCK WIRING
 Specifications
Voltages
85 - 132V AC 50/60Hz
21k / 50Hz
Impedance
Input
18k / 60Hz
6.2mA 110V AC/60Hz
Current
4.7mA 100V AC/50Hz
Circuit isolation
Photocoupler
Operation indication
LED of base unit
OFF  ON
80V 3.8mA
Switch Rating
ON  OFF
30V 1.7mA
Response time
30ms or less
Signal input supply
24V DC 3mA/1pt
 Typical wiring
24 +
1
3
COM1
5
24 -
0
2
COM1
4
Fuse
Signal
DC Power
Supply
8. OUTPUT BLOCKS WIRING
 Outputs specification
RELAY
TRIAC
Switched voltages
Less than 250V AC 30V DC Between 85 - 242V AC
Circuit isolation
By relay coil
Photocoupler
LED is lit when output is
Operation indication LED is lit when coil is active.
active.
resistive
2A/pt 8A/4pts(com)
0.3A/pt 0.8A/4pts(com)
Maximum
15VA, 100V AC
inductive
80VA
load
36VA, 240V AC
indicator
100W
30W
1mA, 100V AC
Leakage current
2mA, 200V AC
0.4VA, 100V AC
Minimum load
2mA 5V DC
1.6VA, 200V AC
OFFON
Less than 2ms
Response
Approx. 10ms
time
ONOFF
Less than 12ms
Indicator input supply
24V DC 5mA/1pt
24V DC 7mA/1pt
 Relay output blocks FX-16EYR-ES-TB/UL, FX-16EYR-TB wiring
PLC
OUTPUT No.
COM
COM
5
7
COM
4
6
COM
Fuse
MC2
MC1
M
M
C
C
1
2
24V DC
COM
Terminal blocks are not equipped with built-in fuses. In order to prevent breakdown of circuits caused by
COM
5
7
COM
load short-circuit, provide a fuse of 5 to 10 A for every four points.
4
6
COM
[ DC LOAD ]
Fuse
MC2
MC1
M
M
C
C
1
2
Hardware Manual or the FX
Hard-
2C
2NC
[ AC LOAD ]
The standard life time of contactors and solenoid valves against AC inductive load is 500,000 times of
actuation against 35 VA.
The table below shows the guideline of the life time of relays based on the result of the life time test per-
formed in our company.
Have in mind that the life time of a relay contact becomes considerably shorter even in the condition below
if the rush current is shut down.
LOAD CAPACITY
(Test condition: ON for 1 second
and OFF for 1 second)
0.35A / 100V AC
35VA
0.17A / 200V AC
COM3,
0.8A / 100V AC
COM4
80VA
7
COM2
0.4A / 200V AC
6
COM2
1.2 / 100V AC
120VA
AC Power
0.6A / 200V AC
Supply
Fuse
 Triac output block FX-16EYS-ES-TB/UL wiring
PLC
OUTPUT No.
TRANSISTOR
5 - 30V DC
Photocoupler of base unit
LED is lit when output is
active.
24V DC
0.5A/pt 0.8A/4pts(com)
Terminal blocks are not equipped with built-in fuses. In order to prevent breakdown of circuits caused by
12W 24V DC
load short-circuit, provide a fuse of 5 to 10 A for every four points.
[ MINUTE CURRENT LOAD ]
1.5W 24V DC
0.1mA 30V DC
Approx. 0.2ms
[ OUTPUT CURRENT ]
Approx. 1.5ms
The current of 0.3 A can flow in each output point. However, in order to restrict temperature rise, flow 0.8
24V DC 7mA/1pt
A to every four output points (= 0.2 A per point on an average). When turning on and off frequently a load
with large rush current, set the square average current to 0.2 A or less.
##
0
1 2 3
##
4
5 6 7
&&
0
1 2 3
&&
4 5 6 7
Power supply
for relays
COM
COM
COM
24+
1
3
5
7
1
3
5
1
2
3
COM
COM
COM
24-
0
2
4
6
0
2
4
6
1
2
3
+10%
-15%
DC
AC
5A
5A
Connect a noise suppression diode to a DC inductive load in parallel.
If the diode is not connected, the life time of the contact becomes
considerably shorter.
Select a noise suppression diode whose reverse withstand voltage is
5 to 10 times or more the load voltage and whose current in the for-
ward direction is not less than the load current.
When a surge absorber is connected to an AC inductive load in paral-
lel, noise generation is reduced.
0.1 F capacitor + 100 to 120  resistor
EXAMPLE OF APPLICABLE LOAD
LIFE TIME OF
(Magnetic switch manufactured by
CONTACT
our company)
S-K10 ~ S-K150
3,000,000 times
S-N10 ~ S-N35
1,000,000 times
S-K180 ~ S-K400
200,000 times
S-K600, S-K800
A surge absorber is connected to each output.
##
0
1 2 3
##
4
5 6 7
&&
0
1 2 3
&&
4 5 6 7
Photocoupler
power supply
COM
COM
COM
24+
1
3
5
7
1
3
5
1
2
3
COM
COM
COM
24-
0
2
4
6
0
2
4
6
1
2
3
+10%
85 -
-15%
85 - 242V AC
242V AC
5A
5A
To a neon lamp or a minute current load of 0.4VA/100V AC, 1.6VA/200V
AC or less, connect a surge absorber in parallel.
×
×
 Transistor output blocks wiring
FX-16EYT-ESS-TB/UL (source)
PLC
OUTPUT No.
##
0
1 2 3
Photocoupler
power supply
COM
7
4
COM
4
24+
1
24-
0
2
+10%
24V DC
-15%
FX-16EYT-ES-TB/UL, FX-16EYT-TB (sink)
PLC
OUTPUT No.
##
0
1 2 3
Photocoupler
power supply
24+
1
24-
0
2
+10%
24V DC
-15%
Terminal blocks are not equipped with built-in fuses. In order to prevent breakdown of circuits caused by
load short-circuit, provide a fuse of 2 A for every four points.
[ ON VOLTAGE ]
The ON voltage of an output transistor is approximately 1.5 V.
When driving a semiconductor device, etc., pay attention to the input voltage characteristics of the used
device.
COM
7
4
COM
4
Manual number : JY992D50401
Manual revision: L
Date
HEAD OFFICE: TOKYO BUILDING, 2-7-3 MARUNOUCHI, CHIYODA-KU, TOKYO 100-8310, JAPAN
JY992D50401L
A surge absorber is connected to each output.
##
4
5 6 7
&&
0
1 2 3
&&
4 5 6 7
COM
COM
COM
COM
3
5
7
1
3
5
7
1
2
3
4
COM
COM
COM
COM
4
6
0
2
4
6
1
2
3
4
5 - 30V DC
5 - 30V DC
2A
2A
A surge absorber is connected to each output.
##
4
5 6 7
&&
0
1 2 3
&&
4 5 6 7
COM
COM
COM
COM
3
5
7
1
3
5
7
1
2
3
4
COM
COM
COM
COM
4
6
0
2
4
6
1
2
3
4
5 - 30V DC
5 - 30V DC
2A
2A
: May 2022
Effective May 2022
Specifications are subject to
change without notice