7

Operating Modes

Before the desired operating mode can be set, the AS-Interface-Handheld must be switched
on by pressing the ADR button.
The desired operating mode is set by pressing the MODE button. Press the MODE button until
the desired operating mode is displayed in the LCD.
The AS-Interface-Handheld APG-02 supports the following operating modes.
:
Display in
Operating mode
the LCD
Addressing mode
ADDR
Read ID-code
ID
Read and write ID-code 1
ID1
Read ID-code 2
ID2
Read IO-code
IO
Read and write data
DATA
Display and write parameters
PARA
Read the peripheral fault flag
PERI
Changing the variable values in running processes can cause personal
injury and damage to equipment when function disturbances or pro-
gram errors occur.
Before executing the functions DATA or PARA make sure that no dan-
gerous conditions can occur.
Leuze electronic
Comments
Read and write AS-Interface slave
addresses
Read and write input or output
data of an AS-Interface slave
Display and write AS-Interface
slave parameters
APG-02
Operating Modes
11