Mounting Instructions, Mounting Options - Beckhoff SCT Series Documentation

Ring-type current transformer for differential current 0...2 a, type b/b+ (all-current sensitive), iso62020-1 conform
Hide thumbs Also See for SCT Series:
Table of Contents

Advertisement

4.1

Mounting instructions, mounting options

• Make sure that the working environment is safe during assembly, maintenance and installation work.
Interrupt the power supply of the primary conductor and secure against being switched on again
inadvertently.
• Install the current transformer on the primary conductor.
• To do this, feed the primary conductor through the opening of the current transformer housing
• The device can be fastened directly to the primary conductor or alternatively to a mounting plate. Use
the fastening materials included in the scope of delivery for this.
Fig. 16: Mounting SCT5xxx
• Fastening the base plate with screws in the four holes
• Free suspension on the cable with the help of cable ties through the hooks on the back for attachment
• All current-carrying conductors/lines must be routed together through the measuring current
transformer [} 29], see Fig, "Use in single-phase and 3- and 4-pin three-phase systems".
• An existing protective conductor [} 29] must not be routed through the transformer
• Bending of the primary conductors may only take place from the specified minimum distance. The
bending radii specified by the manufacturers must be observed.
Fig. 17: Calculation bending primary conductor: *distance to 90° angle = 2x outer diameter
• The conductors are to be centered in the measuring transformer
SCT5xxx
Version: 1.0
Commissioning
27