Sequence For Trouble Diagnosis - Samsung DH052EAMG Service Manual

System air conditioner
Table of Contents

Advertisement

12-3 Sequence for trouble diagnosis

12-3-1 Outdoor temp. sensor(OPEN/SHORT)
Outdoor unit display
Indoor unit display
How to determine
Reason of error
Does the out temperature
sensor connected to PCB?
(CN41)
Yes
Measure the resistance value
between two terminals after
separating the out temp. sensor
connector from PCB
At this time, Is largely
deviate the resistance value from side
table value?
No
Check the out temp.
sensor is normal or not by use of
out data display part
➞ Check the temp. data is
normal or not after pressing K4 3 times.
At this time, is occurred the difference
between the out temp. and data?
Yes
Reoperation after PCB replacement
Samsung Electronics
All manuals and user guides at all-guides.com
(Outdoor temp. sensor OPEN/SHORT error)
(Operation)
(Timer)
Disconnection and short of outdoor temp. sensor
Disconnection or leak of applied sensor
(Airflow)
(Filter)
No
Reoperation
after connect to
connector PCB
Yes
Outdoor unit thermistor
is defective(replace)
No
PCB and sensor are normal.
To perform the test
operation by use of K2
Temp.
Resistance
(˚C)
(kΩ)
70
2.2
60
3.0
50
4.2
40
5.8
30
8.3
20
12.1
10
18.0
0
27.3
-10
43.0
12-6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents