MEMSHIELD 4 INSTALLATION INSTRUCTIONS FOR 400A PANELBOARDS/ PAN ASSEMBLIES
EM4PB840, EM4PB1440, EM4PB1840
EM4PBP840, EM4PBP1440, EM4PBP1840
Instruction Leaflet LT1222 (02/19)
IMPORTANT NOTES
1. This product should be installed, commissioned and maintained by or under the supervision of a competent electrician in
accordance with current electrical engineering Codes of Practice, Requirements for the Electrical Installations (IET Wiring Regulations
BS7671), Construction (Design and Management) Regulations, HSG150 – Health and Safety in Construction, Statutory requirements
and any Specific instruction issued by the Company.
2. After completing the installation and testing of this product it is essential that this leaflet is drawn to the attention of the person
responsible for its future operation and maintenance, and is at all times available for ready reference.
3. The notes assume throughout that the product is disconnected from the supply. It is essential that this is done before any work is
carried out.
4. These Panelboards are only designed for use with EATON MCCBs. Failure to comply will result in invalid warranty and certification.
Panelboard's are supplied as Bottom Entry and Form 4 Type 6 Group Mounted without modification
Incoming Modules
400A Incoming MCCB EM4PBK404
Incoming
mount
General Note: When fixing M5 thread forming
screws tightening torque is 3.8 Nm
400A Incoming Neutral EM4PBNK40
Remove
incoming
mount.
Fit shield
Fit neutral
Bottom
Entry
400A Incoming Direct Cable EM4PBK404L
30Nm
Fit
Mount
30Nm
N
L1
31Nm
Remove
for access
31Nm
Remove
for access
L3
L2
L3
L2
L1
N
Secure
all
shields
4 Pole - Bottom Entry
Form 4 Type 6
3 Pole & Neutral - Bottom Entry
Form 4 Type 6 Group Mounted
Fit
Interphase
shields
4 Pole - Bottom Entry
Form 4 Type 6 Group Mounted
Click cover shield in to
incoming cover aperture
Secure
all
shields
Secure
all
shields