Daikin FTXG20LV1BW Service Manual page 73

Inverter pair wall mounted type l-series
Hide thumbs Also See for FTXG20LV1BW:
Table of Contents

Advertisement

SiBE041401E
Troubleshooting
Check No.02
Check the power supply
Refer to P.94
voltage.
Turn off the power and
rotate the fan by hand.
Turn on the power and
start operation.
Service Diagnosis
Be sure to turn off the power switch before connecting or disconnecting
Caution
connectors, or parts may be damaged.
Is the
voltage
NO
fluctuation
within ±10% from
the rated
value?
YES
NO
Does the fan
rotate smoothly?
YES
Turn off the power and
NO
disconnect the fan motor
Does the fan
connector, then turn the
rotate?
power on.
YES
Stop the fan motor.
Check No.02
Check the output of the
fan motor connector.
NO
Rotation pulse
generated?
YES
Note: The motor may break when the
Check No.02
Check the output of the
fan motor connector
Motor
NO
power supply
voltage 310 ~ 340
VDC?
YES
Motor
NO
control voltage 15
VDC generated?
YES
Rotation
NO
command voltage
1 ~ 6.5 VDC?
YES
NO
Rotation pulse
generated?
YES
Troubleshooting
Correct the power
supply.
Replace the indoor
fan motor.
motor connector is disconnected
while the power is turned on.
(Be sure to turn off the power
before reconnecting the
connector.)
Replace the indoor
unit PCB.
Replace the indoor
unit PCB.
Replace the indoor
unit PCB.
Replace the indoor
fan motor.
Replace the indoor
unit PCB.
Replace the indoor
fan motor.
Replace the indoor
unit PCB.
(R19750)
62