8 APPENDIX
8.5

Current draw and Thermal dissipation specifications

The following tables contain information on measured current consumption as well as calculated heat dissipation
at three states: 1) Stand-by/idling; 2) Normal operation (1/8 of rated power); and 3) at extreme heavy duty
operation (Max. power).
Level
Load
Rated power
115 VAC
Standby with remote power off via NomadLink
Powered on, idling.
Pink noise (1/8
8 Ω / Ch.
1200 x 4
rated power)
16 Ω / Bridged
2400 x 2
4 Ω / Ch.
1700 x 4
8 Ω / Bridged
3400 x 2
2 Ω / Ch.
1200 x 4
4 Ω / Bridged
2400 x 2
100 V / Ch.
1600 x 4
200 V / Bridged
3200 x 2
Pink noise (1/4
8 Ω / Ch.
1200 x 4
rated power)
16 Ω / Bridged
2400 x 2
*3)
4 Ω / Ch.
1700 x 4
8 Ω / Bridged
3400 x 2
4 Ω / Ch.
1200 x 4
8 Ω / Bridged
2400 x 2
100 V / Ch.
1600 x 4
200 V / Bridged
3200 x 2
Mains connector, 230 V CE version
16 A, CEE7
Mains connector, 115 V ETL version
20 A / 5-20P
*1) The amplifi er's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and
specifi ed here is what is known as the "Active Power" in the amplifi er providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measured at maximum power before amplifi er protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated
power. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be
tripped even if operation is in excess of max. ratings.
Level
Load
Rated power
115 VAC
Standby with remote power off via NomadLink
Powered on, idling.
Pink noise (1/8
8 Ω / Ch.
1000 x 4
rated power)
16 Ω / Bridged
2000 x 2
4 Ω / Ch.
1200 x 4
8 Ω / Bridged
2400 x 2
2 Ω / Ch.
600 x 4
4 Ω / Bridged
1200 x 2
100 V / Ch.
900 x 4
200 V / Bridged
1800 x 2
Pink noise (1/4
8 Ω / Ch.
1000 x 4
rated power)
16 Ω / Bridged
2000 x 2
*3)
4 Ω / Ch.
1200 x 4
8 Ω / Bridged
2400 x 2
4 Ω / Ch.
600 x 4
8 Ω / Bridged
1200 x 2
100 V / Ch.
900 x 4
200 V / Bridged
1800 x 2
Mains connector, 230 V CE version
16 A, CEE7
Mains connector, 115 V ETL version
20 A / 5-20P
*1) The amplifi er's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and
specifi ed here is what is known as the "Active Power" in the amplifi er providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measured at maximum power before amplifi er protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated
power. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be
tripped even if operation is in excess of max. ratings.
28 C Series C 68:4, C 48:4, C 28:4 and C 16:4 Operation Manual
C 68:4
Line Current *2)
Watt *1)
Thermal dissipation
230 VAC
In
Out
Dissipated
BTU/hr
kCal/hr
0
0
0
0
0
133
0
133
454
114
Amp (I)
Watt
16.0
8.0
1123
600
523
1784
450
22.4
11.2
1578
850
728
2484
626
21.2
10.6
1378
600
778
2655
669
21.0
10.5
1463
800
663
2262
570
32.6
16.3
2429
1600
829
2829
713
38.8
19.4
2697
1700
997
3402
857
35.2
17.6
2296
1200
1096
3740
942
35.4
17.7
2605
1600
1005
3429
864
C 48:4
Line Current *2)
Watt *1)
Thermal dissipation
230 VAC
In
Out
Dissipated
BTU/hr
kCal/hr
0
0
0
0
0
123
0
123
420
106
Amp (I)
Watt
13,8
6,9
945
500
445
1518
383
17,4
8,7
1171
600
571
1948
491
12,4
6,2
769
300
469
1600
403
13,2
6,6
840
450
390
1331
335
28,2
14,1
2116
1333
783
2670
673
30,6
15,3
2168
1200
968
3303
832
21,6
10,8
1368
600
768
2620
660
26,4
13,2
1827
1200
627
2139
539
C 28:4
Level
Load
Rated power
Line Current *2)
Watt *1)
115 VAC
230 VAC
In
Out
Dissipated
Standby with remote power off via NomadLink
0
0
Powered on, idling.
123
0
Amp (I)
Watt
Pink noise (1/8
8 Ω / Ch.
700 x 4
11.6
5.8
727
350
rated power)
16 Ω / Bridged
1400 x 2
4 Ω / Ch.
700 x 4
13.0
6.5
775
350
8 Ω / Bridged
1400 x 2
2 Ω / Ch.
300 x 4
9.4
4.7
529
150
4 Ω / Bridged
600 x 2
100 V / Ch.
700 x 4
10.4
5.2
663
350
200 V / Bridged
1400 x 2
Pink noise (1/4
8 Ω / Ch.
700 x 4
24.0
12.0
1589
933
rated power)
16 Ω / Bridged
1400 x 2
*3)
4 Ω / Ch.
700 x 4
20.8
10.4
1359
700
8 Ω / Bridged
1400 x 2
4 Ω / Ch.
300 x 4
14.0
7.0
843
300
8 Ω / Bridged
600 x 2
100 V / Ch.
700 x 4
21.4
10.7
1458
933
200 V / Bridged
1400 x 2
Mains connector, 230 V CE version
16 A, CEE7
Mains connector, 115 V ETL version
20 A / 5-20P
*1) The amplifi er's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and
specifi ed here is what is known as the "Active Power" in the amplifi er providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measured at maximum power before amplifi er protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated
power. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be
tripped even if operation is in excess of max. ratings.
C 16:4
Level
Load
Rated power
Line Current *2)
Watt *1)
115 VAC
230 VAC
In
Out
Dissipated
Standby with remote power off via NomadLink
0
0
Powered on, idling.
129
0
Amp (I)
Watt
Pink noise (1/8
8 Ω / Ch.
400 x 4
8.6
4.3
526
200
rated power)
16 Ω / Bridged
800 x 2
4 Ω / Ch.
300 x 4
8.2
4.1
485
150
8 Ω / Bridged
600 x 2
2 Ω / Ch.
n.r.
4 Ω / Bridged
n.r.
100V / Ch.
400 x 4
7.6
3.8
463
200
200V / Bridged
800 x 2
Pink noise (1/4
8 Ω / Ch.
400 x 4
16.2
8.1
1046
533
rated power)
16 Ω / Bridged
800 x 2
*3)
4 Ω / Ch.
300 x 4
15.2
7.6
953
400
8 Ω / Bridged
600 x 2
2 Ω / Ch.
n.r.
4 Ω / Bridged
n.r.
100 V / Ch.
400 x 4
14.4
7.2
944
533
200 V / Bridged
800 x 2
Mains connector, 230 V CE version
16 A, CEE7
Mains connector, 115 V ETL version
15 A / 5-15P
*1) The amplifi er's PSU operates as a non-resistive load, so the calculation "Volts x Amps = Watts" would not be correct. Instead, measured and
specifi ed here is what is known as the "Active Power" in the amplifi er providing useful, real-world values of power consumption and heat dissipation.
*2) Current draw fi gures measured at 230 V. 115 V fi gures are 230 V fi gures multiplied by two.
*3) Figures measured at maximum power before amplifi er protection and limiter features are engaged. Typically this is between 1/4 and 1/3 of rated
power. Note that the max. power condition is very extreme and will not occur during normal operation. Also note that the mains breaker will not be
tripped even if operation is in excess of max. ratings.
C Series C 68:4, C 48:4, C 28:4 and C 16:4 Operation Manual 29
APPENDIX 8
Thermal dissipation
BTU/hr
kCal/hr
0
0
0
123
420
106
377
1286
324
425
1450
365
379
1293
326
313
1068
269
656
2237
564
659
2249
567
543
1853
467
525
1790
451
Thermal dissipation
BTU/hr
kCal/hr
0
0
0
129
440
111
326
1112
280
335
1143
288
263
897
226
513
1749
441
553
1887
475
411
1401
353