PEERLESS PureFire PF-80 Installation, Operation & Maintenance Manual page 72

Rev 2
Table of Contents

Advertisement

BOILER DIMENSIONS & RATINGS
Table 12.4: P
F
®
Main Control Specifications
URE
IRE
SERIES PEERLESS
Power Supply
Fuse (5650)
Blower Voltage
Gas Valve Voltage
Thermostat Contacts
DHW Contacts
Flame Current Limits
Temperature Sensors
Standards
Table 12.5: Electrical Ratings
Supply
Boiler
Voltage
Model
(-15%, +10%)
PF-50
120 VAC
PF-80
120 VAC
PF-110
120 VAC
PF-140
120 VAC
PF-200
120 VAC
PF-210
120 VAC
PF-300
120 VAC
PF-399
120 VAC
70
®
PUREFIRE
120 VAC Nominal (102-132 VAC); 60 Hertz (40-70 Hz) Phase Neutral
3.15 Amp, 250 VAC
120 VAC
120 VAC
24 VAC
24 VAC
Minimum (running): 2.8 µA
Minimum (ignition): 3.1 µA
Maximum: 10 µA
All P
F
URE
IRE
They operate on 5 VDC.
Supply Sensor: 14°F (-10°C) to 244°F (118°C)
Return Sensor : 14°F (-10°C) to 244°F (118°C)
Flue Sensor: 50°F (10°C) to 280°F (138°C)
Outdoor Sensor: -40°F (-40°C) to 185°F (85°C)
Optional Sensors
DHW Sensor: 14°F (-10°C) to 244°F (118°C)
System Sensor : 14°F (-10°C) to 244°F (118°C)
Europe: CE EN298
North America: ANSI Z21.20 / CSA C22.2
®
PUREFIRE
SERIES PEERLESS
Blower
Frequency
Voltage
Current
(±1.2 hz)
(VAC)
(Amps)
60 hz
120
60 hz
120
60 hz
120
60 hz
120
60 hz
120
60 hz
120
60 hz
120
60 hz
120
®
MAIN CONTROL SPECIFICATIONS
NTC thermistors are 12k Ω @ 77°F (25°C).
®
®
ELECTRICAL RATINGS
Gas Valve
Voltage
Current
(VAC)
(Amps)
0.53
120
0.09
0.53
120
0.09
0.78
120
0.09
0.71
120
0.09
2.58
120
0.09
2.58
120
0.09
2.58
120
0.21
2.58
120
0.21
Pumps
Max Total
Service
Max.
Voltage
Current to
Current
(VAC)
Boiler
(Amps)
120
2.48
3.15
120
2.48
3.15
120
2.23
3.15
120
2.30
3.15
120
20.00
22.67
120
20.00
22.67
120
20.00
22.79
120
20.00
22.79