Tyco TY-FRB Series Quick Start Manual

Tyco TY-FRB Series Quick Start Manual

5.6 and 8.0 k-factor conventional (old style) sprinklers quick response
Hide thumbs Also See for TY-FRB Series:

Advertisement

Quick Links

Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500
Series TY-FRB — 5.6 and 8.0 K-factor
Conventional (Old Style) Sprinklers
Quick Response
General
Description
The Series TY-FRB, 5.6 and 8.0 K-fac-
tor, Conventional Sprinklers described
in this data sheet are quick response -
standard coverage, decorative 3 mm
glass bulb
type spray sprinklers.
These sprinklers are intended to be
installed either pendent or upright, and
in either position, they produce a
spherical water discharge pattern with
approximately 50% of the discharge
directed upwards and approximately
50% of the discharge directed down-
wards.
Conventional sprinklers are generally
used with Ordinary and Extra High
Hazard Class Systems, as defined by
the automatic sprinkler system instal-
lation rules of the country and authority
having jurisdiction. The NFPA permits
the use of "Old Style Sprinklers" where
special construction features require a
unique water distribution; for the pro-
tection of fur vaults; or, the replace-
ment of similar sprinklers that had
been installed prior to 1955.
Corrosion resistant coatings, where
applicable, are utilized to extend the
life of copper alloy sprinklers beyond
that which would otherwise be ob-
tained when exposed to corrosive at-
mospheres. Although corrosion resis-
tant coated sprinklers have passed the
standard corrosion tests of the appli-
IMPORTANT
Always refer to Technical Data
Sheet TFP700 for the "INSTALLER
WARNING" that provides cautions
with respect to handling and instal-
lation of sprinkler systems and com-
ponents. Improper handling and in-
stallation can permanently damage
a sprinkler system or its compo-
nents and cause the sprinkler to fail
to operate in a fire situation or cause
it to operate prematurely.
Page 1 of 4
cable approval agencies, the testing is
not representative of all possible cor-
rosive atmospheres. Consequently, it
is recommended that the end user be
consulted with respect to the suitability
of these coatings for any given corro-
sive environment. The effects of ambi-
ent temperature, concentration of
chemicals, and gas/chemical velocity,
should be considered, as a minimum,
along with the corrosive nature of the
chemical to which the sprinklers will be
exposed.
WARNINGS
The Series TY-FRB Sprinklers de-
scribed herein must be installed and
maintained in compliance with this
document, as well as with the applica-
ble standards of the National Fire Pro-
tection Association, in addition to the
standards of any other authorities hav-
ing jurisdiction. Failure to do so may
impair the performance of these de-
vices.
The owner is responsible for maintain-
ing their fire protection system and de-
vices in proper operating condition.
The installing contractor or sprinkler
manufacturer should be contacted
with any questions.
Model/Sprinkler
Identification
Numbers
TY3631 -
5.6K, 1/2"NPT
TY4631 -
8.0K, 3/4"NPT
JULY, 2004
Technical
Data
Approvals
UL and C-UL Listed.
LPCB, VdS and NYC Approved.
(Refer to Table A for complete approval
information including corrosion resis-
tant status.)
Maximum Working Pressure
175 psi (12,1 bar)
Discharge Coefficient
1/2
K = 5.6 GPM/psi
(80,6 LPM/bar
1/2
K = 8.0 GPM/psi
(115,2 LPM/bar
Temperature Ratings
Refer to Table A
Finishes
Sprinkler: Refer to Table A
Physical Characteristics
Frame . . . . . . . . . . . . Bronze
Button . . . . . . . .
Brass/Copper
Sealing Assembly . . . . . . . . . .
. . . . . . Beryllium Nickel w/Teflon†
Bulb
. . . . . . . . . . . . . . Glass
Compression Screw . . . . . Bronze
Deflector . . . . . . . . . . . Copper
1/2
)
1/2
)
TFP666

Advertisement

loading
Need help?

Need help?

Do you have a question about the TY-FRB Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Tyco TY-FRB Series

  • Page 1 Technical Services: Tel: (800) 381-9312 / Fax: (800) 791-5500 Series TY-FRB — 5.6 and 8.0 K-factor Conventional (Old Style) Sprinklers Quick Response cable approval agencies, the testing is General not representative of all possible cor- rosive atmospheres. Consequently, it Description is recommended that the end user be consulted with respect to the suitability The Series TY-FRB, 5.6 and 8.0 K-fac-...
  • Page 2 Page 2 of 4 TFP666 ESCUTCHEON 7/16" (11,1 mm) ESCUTCHEON 1/2" (12,7 mm) PLATE SEATING NOMINAL PLATE SEATING NOMINAL 1/2" 3/4" SURFACE MAKE-IN SURFACE MAKE-IN 2-3/16" 2-1/4" (55,6 mm) (57,2 mm) 1-1/2" 1-1/2" (38,1 mm) (38,1 mm) WRENCH WRENCH FLATS FLATS SHOWN CROSS SECTION...
  • Page 3 4. Approved by the City of new York under MEA 354-01-E. 5. VdS Approved (For details contact Tyco Fire & Building Products, Enschede, Netherlands, Tel. 31-53-428-4444/Fax 31-53-428-3377). 6. Where Polyester Coated and Lead Coated Sprinklers are noted to be UL and C-UL Listed, the sprinklers are UL and C-UL Listed as Corrosion Resistant Sprinklers.
  • Page 4 Tyco Fire Products shall not be responsible for sprinkler system design errors or inaccurate or incomplete information supplied by Buyer or Buyer’s representatives. IN NO EVENT SHALL TYCO FIRE TYCO FIRE PRODUCTS, 451 North Cannon Avenue, Lansdale, Pennsylvania 19446...

This manual is also suitable for:

Ty3631Ty4631