Installation
Space Temperature
Averaging
(ReliaTel™ only)
Space temperature averaging is
accomplished by wiring a number of
remote sensors in a series/parallel
circuit.
Using the BAYSENS016* or
BAYSENS017*, at least four sensors
are required to accomplish space
temperature averaging.
Figure 36.
Examples
RT-SVX21F-EN
Example #1 illustrates two series
circuits with two sensors in each
circuit wired in parallel. The square
of any number of remote sensors is
required.
Example #2 illustrates three sensors
squared in a series/parallel circuit.
Using BAYSENS032*, two sensors
are required to accomplish space
temperature averaging.
Example #3 illustrates the circuit
required for this sensor.
Figure 7,
p. 33
lists the temperature versus
resistance coefficient for all sensors.
31