Configurable Digital Output
Module
The configurable digital output
module also has six outputs. Like
the digital output module with the
rotary switch, it is available with
optocoupler and relay outputs.
Unlike the modules with the rotary
switch, however, the outputs are
assigned using a software tool
rather than a selector switch. The
BDA can be used as configuration
software. The outputs can be
assigned the events in the table
opposite using drop-down fields.
The first three module outputs can
be assigned up to six events. All
of these events operate in parallel.
This triggers, for example, a type
of group signal when the circuit
breaker is either impending trip
mode or a phase unbalance
warning is present.
The last three outputs can only be
assigned one of the events directly.
Configuration events include
status signals, warnings, tripped
indication, over/under setpoint
status, waveform buffer triggers,
and the active parameter set.
The module outputs can be set
remotely using communications.
WL PROFIBUS Communication and Electronic Accessories • July 2004
Communication-capable Circuit Breakers
These events are available for the digital, configurable output module (part 1)
Status
Alarms
Trips
PROFIBUS output bits
Table 2-17
The events in this table (part 1) and the following table (part 2) are available on the
CubicleBUS. These can be output via the configurable digital output module.
WL Circuit Breaker
Circuit breaker closed
Circuit breaker open
Storage spring charged
Ready-to-close
Group warning
Group trip
PROFIBUS write protection active
PROFIBUS communication OK
Overload
Overload in N-conductor
Load shedding
Load restoring
Ground fault alarm
Overtemperature
ETU error
Phase unbalance - current
Long-time (L)
Short-time (S)
Instantaneous short-circuit (I)
Ground fault (G)
Overload in neutral conductor
Phase unbalance - current
Phase unbalance - voltage
Under frequency
Over frequency
Undervoltage
Overvoltage
Active power in normal direction
Active power in reverse direction
Total harmonic distortion - current
Total harmonic distortion - voltage
Reversal of phase rotation direction
PROFIBUS bit 1
PROFIBUS bit 2
PROFIBUS bit 3
PROFIBUS bit 4
PROFIBUS bit 5
PROFIBUS bit 6
Parameter set A active
Parameter set B active
2/26