Breaker Data Adapter (BDA)
WL Circuit Breaker
When the boot-up process is
complete, the DEVICE LED switches
to green, while the CubicleBUS LED
switches to green or is extinguished,
depending on the connection.
If the BDA is not supplied power via
the CubicleBUS of the WL, it must be
activated via an external 24V DC
power supply. Siemens SITOP
24V DC power supplies are suitable
for this purpose.
Other 24V DC power supply units
that supply the required power can
also be used.
4/7
Technical data for the BDA and BDA Plus
Min./Max. operating voltage
Current input from the CubicleBUS or power supply
unit min./max.
Power loss min. / typ. /max.
Dimensions W/H/D
Weight
Operating temperature range
Figure 4-4
This table provides technical data for the BDA and BDA Plus
WL PROFIBUS Communication and Electronic Accessories • July 2004
19.2V / 28.8V
100mA / 300mA
3W / 5W / 7W
82mm /153mm / 38mm
0.38 kg
0 to 55°C