Download Print this page
Payne PH14 B Series Wiring Diagram

Payne PH14 B Series Wiring Diagram

Split-system heat pump with r-410a refrigerant 1-1/2 - 5 nominal tons

Advertisement

Quick Links

CONNECTION DIAGRAM
*CHS
*CH
BLK
BLK
BLK
or
RED
CONT
RED or BLK
11
21
L1
208/230 1Ø
23
23
L2
POWER
SUPPLY
EQUIP GND
BLK
BLK
*DTS
*LPS
RED
YEL/PNK
OR
BLUE
YEL/PNK
OF1
30 60
90
W1
OF2
SPEED UP
C
Y
O
W2
R
YEL
WHT
BLK
RED
ORN
INDOOR UNIT
C
Y
O
W2
R
E
L
W3
G
TERMINAL BLOCK
THERMOSTAT
C
Y
O
W2
R
E
L
G
-LEGEND-
FACTORY POWER WIRING
FIELD POWER WIRING
FACTORY CONTROL WIRING
FIELD CONTROL WIRING
CONDUCTOR ON CIRCUIT BOARD
COMPONENT CONNECTION
1/4-IN QUICK CONNECT TERMINALS
FIELD SPLICE
JUNCTION
CAP
CAPACITOR
*CH
CRANKCASE HEATER
*CHS
CRANKCASE HEATER SWITCH
COMP
COMPRESSOR
CONT
CONTACTOR
CB
CIRCUIT BOARD
DFT
DEFROST THERMOSTAT
DR
DEFROST RELAY & CIRCUITRY
*DTS
DISCHARGE TEMP. SWITCH
*HPS
HIGH PRESSURE SWITCH
*LLS
LIQUID LINE SOLENOID VALVE
*LPS
LOW PRESSURE SWITCH
OFM
OUTDOOR FAN MOTOR
RVS
REVERSING VALVE SOLENOID
*SC
START CAPACITOR
*SR
START RELAY
*ST
START THERMISTOR
* MAY BE FACTORY OR FIELD INSTALLED
Fig. 1 – Wiring Diagram — Model sizes 1- -1/2 - - 4 tons, 208/230- -1
Wiring Diagram
BLU
BLK
+t°
CAP
COMP
BLU
YEL
S
*ST
C
H
*SC
BLK
C
YEL
BRN
R
1
YEL
F
YEL
*SR
YEL
BRN
OFM
YEL
BRN
RED
*HPS
OR
BLU/PNK
BLU/PNK
BLUE
Y
YEL
T1
C
BRN
ORN
C
RVS
O
ORN
DFT
PNK
R
DFT
PNK
INDOOR
(NOTE #5)
NOTES:
1. Compressor and fan motor furnished with
inherent thermal protection.
2. To be wired in accordance with National
Electric Code (N.E.C.) and local codes.
3. N.E.C. class 2, 24V circuit, min. 40 VA required,
60 VA on units installed with LLS.
4. Use copper conductors only, from disconnect to unit.
5. Must use thermostat and sub-base as stated
in pre-sale literature.
6. If indoor section has a transformer with a
grounded secondary, connect the grounded
side to "C" on the circuit board.
7. If any of the original wire, as supplied, must
be replaced, use the same or equivalent wire.
8. Check all electrical connections inside control
box for tightness.
9. Do not attempt to operate unit until service
valves have been opened.
10. Use conductors suitable for at least 75ºC (167ºF).
CAUTION
1. Compressor damage may occur if system is
over charged.
2. This unit is factory charged with R-410A in
accordance with the amount shown on the rating
plate. The charge is adequate for most systems
using matched coils and tubing not over 15 feet
long. Check refrigerant charge for maximum
efficiency. See Product Data Literature for
required Indoor air Flow Rates and for use of
line lengths over 15 feet.
3. Relieve pressure and recover all refrigerant
before system repair or final disposal. Use all
service ports and open all flow-control devices,
including solenoid valves.
4. Never vent refrigerant to atmosphere.
Use approved recovery equipment.
SPLIT- -SYSTEM HEAT PUMP
WITH R- -410A REFRIGERANT
SCHEMATIC DIAGRAM (LADDER FORM)
L1
CONT
11
21
BLU
5
2
EQUIP
2
1
GND
5
*SR
* CHS
DR
* CH
OF1
OF2
RVS
O
O
W2
R
R
DR
Y
Y
T1
C
*LPS
*DTS
90
FIELD SELECTED TIME PERIOD
60
BETWEEN DEFROST CYCLES (MINUTES)
30
SPEED
JUMPERED TEST PINS (USE METAL OBJECT), FIELD SPEED-UP CYCLE
UP
HEAT CYCLE:
DEFROST CYCLE:
CONDENSING UNIT CHARGING INSTRUCTIONS
For use with units using R-410A refrigerant
TABLE I - SUPERHEAT CHARGING TABLE
(SUPERHEAT ºF AT LOW-SIDE SERVICE PORT)
EVAPORATOR ENTERING AIR º F WB.
OUTDOOR
50 52 54 56 58 60 62 64
67
68 70 72 74 76
TEMP ºF
11 11 12 12 12 13 17 20 24 24 25 25 25 25
55
60
6 6 7 7 7
7
12 16 21 22
23 23 23 23
65
- - - - - - - - - -
3
7 12 18 19 21 21 22 22
70
- - - - - - - - - -
- - - -
7 14 16 18 20 20 20
75
- - - - - -
- - - - - - - - 3 11 13 16 18 18 19
- - - - - - - - - - - - - -
- -
*
6 8 12 15 16 17
82
85
- - - - - - - - - - - -
- - - -
4
7 11 14 15 16
- - - - - - - - - - - - - - - -
90
- -
4 8 12 14 15
95
- - - - - - - - - - - - - - - -
- - - -
6 10 12 14
100
- - - - - - - - - - - - - - - -
- - - -
4 8 11 12
- - - - - - - - - - - - - - - -
- - - -
105
3 6 9 11
110
- - - - - - - - - - - - - - - -
- - - - - -
115
- - - - - - - - - - - - - - - - - - - - - -
Where a dash (- -) appears do not attempt to charge system under these
conditions or refrigerant slugging may occur. Charge must be weighed in.
Note: Superheat ºF is at low-side service port, allow a tolerance of +/- 3 ºF
Note: Indoor dry bulb between 70 ºF and 80 ºF
* Optimum performance point, 82 ºF outdoor ambient and (80 ºF dry bulb),
(67 ºF wet bulb) indoor conditions. (DOE B Test Conditions)
TABLE II - REQUIRED SUCTION TUBE TEMPERATURE ºF
(MEASURED AT LOW-SIDE SERVICE PORT)
SUPERHEAT
SUCTION PRESSURE AT SERVICE PORT PSIG.
TEMP. ºF
108 112 117 121 126 131 139 141 146
0
35
37 39
41
43
45
47
39 41
43
45
49
2
37
47
4
39
41 43
45
47
49
51
43 45
47
49
53
6
41
51
8
43
45 47
49
51
53
55
47 49
51
53
10
45
55
57
12
47
49 51
53
55
59
57
51 53
55
57
14
49
59
61
16
51
53 55
57
59
63
61
18
53
55 57
59
61
63
65
20
57 59
61
63
55
65
67
22
57
59 61
63
65
69
67
61 63
65
67
24
59
69
71
26
61
63 65
67
69
71
73
65 67
69
71
28
63
73
75
30
67 69
71
73
77
65
75
PH14*B
1- -1/2 - - 5 NOMINAL TONS
L2
COMP
R
C
S
*SC
*ST
+t°
H
CONT
OFM
C
23
23
F
CAP
C
DFT
DFT
LOGIC
C
CONT
*HPS
90 MIN. ACCELERATED TO 21 SEC.
60 MIN. ACCELERATED TO 14 SEC.
30 MIN. ACCELERATED TO 7 SEC.
10 MIN. ACCELERATED TO 2 SEC.
COOLING ONLY
CHARGING PROCEDURE
1. Operate unit a minimum of 10 minutes
before checking charge.
2. Measure suction pressure by attaching
an accurate gage to suction valve
service port.
3. Measure suction temperature by
attaching an accurate thermistor type
or electronic thermometer to the
suction line at service valve.
4. Measure outdoor air dry-bulb
temperature with a thermometer.
5. Measure indoor air (entering indoor
coil) wet-bulb temperature with a sling
psychrometer.
6. Refer to Table I. Find outdoor
temperature and evaporator entering
5 7 10
air wet-bulb temperature. At this
3
6
8
intersection, note superheat. Where a
dash (- -) appears on table do not
attempt to charge system under these
conditions or refrigerant slugging may
occur. Charge must be weighed in,
adding or removing 0.6 oz/ft of 3/8
liquid line above or below 15 ft.
respectively.
7. Refer to Table II. Find superheat
temperature located in step 6 and
suction pressure. At this intersection
note suction line temperature.
8. If unit has a higher suction line
49
51
temperature than charted temperature,
53
51
add refrigerant until charted
53
55
temperature is reached.
57
55
9. If unit has a lower suction line
57
59
temperature than charted temperature,
remove and recover refrigerant until
59
61
charted temperature is reached.
63
61
10. When adding refrigerant, charge in
63
65
liquid form into the suction service port
67
65
using a flow-restricting device.
67
69
11. If outdoor air temperature or pressure
69
71
at suction valve changes, charge to
73
71
new suction line temperature indicated
73
75
on chart.
75
77
12. This procedure is valid when indoor air
flow is within +/- 21% of its rated cfm
77
79
81
79
339904-101 REV. C

Advertisement

loading

Summary of Contents for Payne PH14 B Series

  • Page 1 PH14*B SPLIT- -SYSTEM HEAT PUMP WITH R- -410A REFRIGERANT 1- -1/2 - - 5 NOMINAL TONS Wiring Diagram CONNECTION DIAGRAM SCHEMATIC DIAGRAM (LADDER FORM) *CHS COMP CONT +t° COMP CONT RED or BLK EQUIP +t° 208/230 1Ø CONT POWER SUPPLY * CHS EQUIP GND * CH...
  • Page 2 Fig. 1 – Wiring Diagram — Model sizes 5 tons, 208/230- -1...
  • Page 3 Fig. 1 – Wiring Diagram — Model sizes 3, 4 and 5 tons, 208/230- -3...
  • Page 4 Fig. 1 – Wiring Diagram — Model sizes 3, 4 and 5 tons, 460- -3 Catalog No. WDPH14NB---03 Payne Heating & Cooling 7310 W. Morris St. Indianapolis, IN 46231 Edition Date: 08/18 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.