Refer to the supplementary operation guide supplied with the Product.
After Power ON, the Status LED on a Clevertest Plus enabled fitting will display a rapid Green or Red
flashing for a period up to 2 minutes.
Luminaires fitted with a dome may require removal of the dome to successfully scan the fitting with a
camera using the CleverSparky App.

Zoneworks, HIVE (HV/HVG) and DATA Monitored Options

Fittings with part numbers
-ZW, -HV, -HVG -DATA
(nodes). These fittings are monitored using either Powerline Carrier Technology that utilize the power
cable to provide data communication, RF transceiver modules operating in the ISM band or a dedicated
data cable to/from data routers installed on a dedicated data trunk connected to a central Server (can also
be connected via Ethernet/Internet/Fibre). Zoneworks software on the server is used to monitor,
coordinate testing and collate test data from each fitting. Zoneworks Fittings can be commissioned by a
single push of the test switch or by scanning the supplied barcode. The LED Test Switch indicator provides
a multifunction indication of the status of the fitting during testing and normal operation:
Option
State
ZW, HV, HVG,
Commissioned
DATA
ZW, DATA
Un-commissioned
Un-commissioned
HV, HVG
With network connectivity
Un-commissioned
HV, HVG
Without network connectivity
ZW, DATA
Emergency Light Test In Progress
HV, HVG
Emergency Light Test In Progress
In the case of the DATA version a 2-way "figure 8" cable and terminal block facilitates the connection to
the DATA network via a multi-drop bus (daisy chain connection). For further information of installation of
a Zoneworks system, please refer to the Zoneworks Users Guide and Commissioning Guide (incl. DATA
version)

DALI EM Option

Luminaires with part numbers having
-DALI
rd
and integration to 3
Party Lighting Control Systems. Before installing the -DALI luminaire, please confirm
that the Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI
fitting will be addressed and configured into the control system by the Lighting Control System
Commissioning Technicians and not Clevertronics.
State
LED Operation
Commissioned/ Un-commissioned
LED on Solid (Green)
Emergency Light Test in progress
LED flashes at 1s On (Yellow) & 1s Off
"IDENTIFY COMMAND"
Lamp and Status LED Flash for 30 seconds
A 2-way "figure 8" cable and terminal block facilitates the connection to the DALI network. DALI
connections are marked as Da Da.
Instruction Sheet Template - V1.3 – Updated 20/01/2022
are fitted with Zoneworks communications modules
LED Operation
LED on Solid (Green)
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
Batt plugged-in: yellow 1s, green 1s
Batt unplugged: red 1s, off 1s
Batt plugged-in: yellow 250mS, green
250mS, yellow 250mS, green 250mS,
green 1s
Batt unplugged: red 250mS, off
250mS, red 250mS,off 250mS, off 1s
LED flashes at yellow 5s , 0ff 1s
LED flashes at yellow 1s , 0ff 1s
are fitted with DALI modules (nodes) that facilitate connection
L10™ LIFELIGHT Recessed Emergency
Installation & Maintenance Instruction Leaflet
Designed in Australia to comply with the
requirements of AS2293.3: 2005 and AS/NZS
CISPR15: 2017
NOTE: Standard product codes with this symbol
enabled with Clevertest Plus capability. Please refer to
the operation guide supplied with the product for details.
Models:
LLIFE-xx-yy-ss-uu-zz
Manual Test
xx = Blank
Zoneworks
xx = ZW
Z/W DATA
xx = DATA
Zoneworks HIVE xx = HV/HVG
DALI Registered.
xx = DALI
Clevertest
xx = CT
(NOTE: -CT Products supplied with the Clevertest Plus Symbol
capability. Please refer to the operation guide supplied with the product for details).
TAMPERPROOF variants use 4 T10 security screws to secure the head

Spare Parts:

1530010
Replacement Battery
1100925
Replacement Emergency Head- white
1100924
Replacement Emergency Head- Black
AUM01370030001
Replacement Emergency Driver
AUM01270310002
Replacement Emergency Driver -DALI
A
UM01870020001
Replacement Emergency Driver -HV
AUM01970100001
Replacement Emergency Driver -HVG

Important:

It is illegal for anyone, except for a licensed electrician to install or maintain this product. Before installation,
ensure that the electricity supply has been switched off and isolated. Installation must be carried out in
accordance with the relevant Australian and International Standards.
Victoria (Head Office & Manufacturing)
Website:
www.clevertronics.com.au
Email:
info@clevertronics.com.au
Phone: +61 3 9559 2700
Fax: +61 3 9559 2799
New South Wales
Phone: +61 2 8805 6400
Fax: +61 2 8805 6444
Queensland
Phone: +61 7 3442 9700
Fax: +61 7 3442 9777
are
South Australia/Northern Territory
Phone: +61 8 8301 8800
Fax: +61 8 8351 8286
Western Australia
Phone: +61 8 9207 0000
Fax: +61 8 9207 0088
New Zealand
Phone: +64 800 548 448
Options:
Dome
ss= D
Tamperproof
yy = TP
Black LED Head
zz= BLK
Cable Option
uu = 5C/ F5C
are activated with Clevertest PLUS
1942013
V2.2
19 May 2022

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the L10 LIFELIGHT LLIFE Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Clevertronics L10 LIFELIGHT LLIFE Series

  • Page 1 Lighting Control System has the capability to monitor DALI Emergency Luminaires. The -DALI Spare Parts: fitting will be addressed and configured into the control system by the Lighting Control System Commissioning Technicians and not Clevertronics. 1530010 Replacement Battery...
  • Page 2 Battery warranty claims, as a result of such Head Diameter: 95mm diameter abuse, are specifically EXCLUDED from Clevertronics warranty terms. Cut-out Hole: 85mm diameter Adaptor Ring: 145mm diameter, suits 125mm hole...

This manual is also suitable for:

Lp lifelight pro clife pro series

Table of Contents