Fujitsu RSG07KPCE Service Manual page 59

Table of Contents

Advertisement

Check point 3. Check the solenoid coil and 4-way valve
Solenoid coil
Remove CN30 from PCB and check the resistance value of coil. Resistance value is about 1.88
kΩ ~ 2.29 kΩ.
→ If it is open or abnormal resistance value, replace solenoid coil.
4-way valve
Check each piping temperature, and the location of the valve by the temperature difference.
If the value location is not proper, replace 4-way valve.
Check point 4. Check the voltage of 4-way valve
Check the voltage CN30 of Main PCB.
→ Check if AC 270 V (AC 230 V -10%) to AC 253 V (AC 230 V +10%) appears at CN30 of Main
PCB.
Heating operation
→ If it is not voltage, Replace Main PCB.
Cooling operation
→ If it is voltage, Replace Main PCB.
Check point 5. Replace main PCB
If Check Point 1 to 4 do not improve the symptom, replace main PCB.
2-18. E: 99. 4-way valve error (Outdoor unit)
End
- (03-25) -
2. Troubleshooting with error code