LG LP070CED Service Manual page 33

Packaged terminal air conditioner/heat pump
Hide thumbs Also See for LP070CED:
Table of Contents

Advertisement

Figure 26
7. Position the condensate tube through existing hole (located
right side of blower deck).
8. Make sure the holes in the condensate tube are facing
inward toward the blower wheel.
9. Lower the discharge deck over the condensate tube and
screw the discharge deck to the chassis with the existing
screws. Replace the discharge screen and screw the
screen to the discharge deck with the existing screws.
10. Using the overflow tube holder and the overflow tube,
hold the tube with the metal holder and screw the holder
to the partition panel with the provided 1/2 inch #8 screw.
(Figures 27 & 28)
Figure 27
Holder
Figure 28
Condensate Tube
Tube
—33—
11. Place the pump bracket onto the end of the pump by
feeding the pump cord through the hole in the bracket and
pushing the bracket onto the threads of the pump. Slide
the supplied washer onto the threads of the pump. Screw
the pump nut onto the threads of the pump and tighten
the nut so that the bracket is secure against the pump.
(Figure 29)
Figure 29
12. Position the pump in the back left corner of the basepan
and screw the pump bracket to the basepan with the
provided two 1/2 inch #8 screws. (Figure 30)
Figure 30
13. Remove the protective adhesive backing from the plastic
U clip and mount the U clip to the plastic condenser
shroud in approximately the position shown. (Figure 31)
14. Snap the provided round plastic grommet into the top
condenser baffle. (Figure 31)
Screws

Hide quick links: