This manual is applied to N3410 series programmable DC power supply, including installation, operation, specifications and other detailed information. The copyright of the manual is owned by NGI. Due to the upgrade of instrument, this manual may be revised without notice in future versions.
NGI shall not be liable for the results caused by the neglect of those instructions. 2.1 Safety Notes Confirm the AC input voltage before supplying power.
±240VDC. The insulation of all wires at the operation site must meet the present voltage requirements. The maximum floating voltage to ground is 240VDC. ± (Using non-insulated short-circuit conductor) N3410 Series Triple-channel Programmable DC Power Supply...
3 Product 3.1 Brief Introduction N3410 series is a triple-channel programmable DC power supply with high performance and high reliability. N3410 is with half 19 inch 2U size, integrating three independent output channels, and supporting both front and rear wiring. It has compact size and elegant appearance.
USB flash drive User manual, software & technical information If any loss or damage, please contact our authorized distributor or NGI. 4. Check the whole instrument. If N3410 chassis is damaged or has abnormal operation, please contact our authorized distributor or NGI.
A ll C H 1 C H 2 C H 3 Figure 1 Front Panel Dimension(mm) 214.0 RS485 AC IN Figure 2 Rear Panel Dimension(mm) Note: For N3411E/N3412E/N3413E, sense terminals are not available. N3410 Series Triple-channel Programmable DC Power Supply...
N 3411E 32V/3A 2C H 6V 3A 1C H × × Enter Unlock Loc k A ll C H 1 C H 2 C H 3 Figure 5 Front Panel Table 4 Number Name Function Device model Displaying model number N3410 Series Triple-channel Programmable DC Power Supply...
Page 10
To turn on/off the output for all three channels A ll Single channel control C H 1 C H 3 To lock/unlock L o c k To confirm En t er To exit To delete To move the cursor N3410 Series Triple-channel Programmable DC Power Supply...
Hunan Next Generation Instrumental T&C Tech. Co., Ltd. 3.4 Rear Panel Introduction RS232 AC IN Figure 6 Rear Panel Table 6 Number Name RS232 interface LAN port Output interface AC power socket Grounding screw N3410 Series Triple-channel Programmable DC Power Supply...
3) Check whether the fuse is burned out. If yes, please replace it. Please use the proper fuse. When replacing, please open the plastic cover at the AC power socket. For more support, please contact NGI. N3410 Series Triple-channel Programmable DC Power Supply...
When this icon shows, it means beeper setting is ON. 5. Channel icon It shows the channel number of three channels. 6. Alarm The protection of specific channel occurs. 7. Channel state There are three states: OFF, CV ON and CC ON. N3410 Series Triple-channel Programmable DC Power Supply...
2. Connect the positive polarity of load wire to the positive output interface, and the negative polarity of load wire to the negative output interface. The wiring method is shown in the figure below. N3410 Series Triple-channel Programmable DC Power Supply...
2. Press button below V/I-Set on the screen and move cursor to voltage/current setting area. 3. Press En t er 4. Input digit by pressing numeric buttons or pressing to move the cursor and rotate to adjust the value. N3410 Series Triple-channel Programmable DC Power Supply...
5. Press to confirm the setting. En t er Figure 9 Voltage/Current Setting 4.3.3 Protect Setting The OVP/OCP setting range of N3410 series is shown below. By default, OVP/OCP is set to the maximum value. Table 7 Model N3411 N3412...
Page 17
When overvoltage/overcurrent protection occurs, please also check whether OVP/OCP setting value is lower than output voltage/current. If this is not the case, please contact our authorized distributor or NGI. Note: When overvoltage/overcurrent occurs, the protection circuit inside N3410 will shut off output. If an active load such as a battery is connected to N3410...
4.3.4.1 Parallel Mode Please press the button below PARALL on the screen and switch to parallel mode. Figure 13 Parallel Mode parallel mode, power supply output 0-6A N3411E/N3413E/N3411/N3411P/N3413/N3413P 0-10A N3412E/N3412/N3412P. power supply output 0-32V N3410 Series Triple-channel Programmable DC Power Supply...
Page 19
. ON icon will show at channel 1 and C H 1 channel 2. The power supply starts output. 4.3.4.2 Series Mode Please press the button below SERIES on the screen and switch to series mode. Figure 15 Series Mode N3410 Series Triple-channel Programmable DC Power Supply...
Page 20
2. The power supply starts output. Note: It is not recommended to use constant current in series mode. 4.3.4.3 Trace Mode Please press the button below TRACE on the screen and switch to trace mode. N3410 Series Triple-channel Programmable DC Power Supply...
Page 21
En t er After completing setting, please press . ON icon will show at channel 1 and C H 1 channel 2. Channel 2 follows channel 1 to output the same voltage and current in N3410 Series Triple-channel Programmable DC Power Supply...
6. Press buttons below Baud Rate/Beeper/Sample Rate/Output Pos separately. 7. Press on Baud Rate/Sound/Sample Rate/Output Pos setting area. En t er 8. Press or rotate to select the required parameter. 9. Press to confirm the setting. En t er N3410 Series Triple-channel Programmable DC Power Supply...
6. Press to confirm the setting. En t er 7. Press button below Timer. 8. Press on Timer setting area. En t er N3410 Series Triple-channel Programmable DC Power Supply...
Figure 21 SEQ Interface Run/Stop Pause/Cont: pause or continue Channel: channel switch Edit: SEQ file edit 4.3.8 SEQ Edit Please press button below Edit on the screen under SEQ interface. N3410 Series Triple-channel Programmable DC Power Supply...
Page 25
Please press button below Save/Load on the screen to enter SEQ Load interface. Please rotate or press to move to the required parameter. There are four parameters: Operation, Position, File name and Start Load. Figure 23 SEQ Load N3410 Series Triple-channel Programmable DC Power Supply...
The Graph interface can display the real-time graph of voltage and current of the specific channel, as shown in the figure below. Figure 24 Graph Interface CH1/CH2/CH3: set displaying or concealing the graph for specific channel Run/Stop N3410 Series Triple-channel Programmable DC Power Supply...
Due to system upgrade or hardware problem, the device may break down. Please do the following necessary inspection to eliminate the troubles, which can save your maintenance and time cost. If the troubles cannot be recovered, please contact NGI. The inspection steps are as below.
≤5mVp-p ≤10mVp-p Voltage Ripple Noise (20Hz ~ 20MHz) ≤1mVrms Voltage Ripple Noise (20Hz ~ 20MHz) ≤3mArms Current Ripple Noise (20Hz ~ 20MHz) Dynamic Characteristics Voltage Rise Time (no load) 20ms 20ms 20ms 20ms N3410 Series Triple-channel Programmable DC Power Supply...
Page 29
Temperature Operating temperature: 0 ℃ -40 ℃ , storage temperature: -20 ℃ ~60 ℃ Operating Environment Altitude <2000m, relative humidity: 5%-90%RH(non-condensing), atmospheric pressure: 80-110kPa Net Weight Approx. 9kg Approx. 11kg Dimension 88.0(H)*214.0(W)*398.0(D)mm 88.0(H)*214.0(W)*446.0(D)mm N3410 Series Triple-channel Programmable DC Power Supply...
Page 30
Voltage Fall Time (full load) 45ms 13ms (90%-10%F.S. Variation Time) Transient Recovery Time ≤1ms Line Regulation-Voltage ≤0.01%+1mV ≤0.01%+3mV Line Regulation-Current ≤0.01%+3mA ≤0.02%+3mA Load Regulation-Voltage ≤0.01%+3mV Load Regulation-Current ≤0.01%+6mA ≤0.02%+3mA DVM Measurement (For N3413P Only) N3410 Series Triple-channel Programmable DC Power Supply...
Page 32
Temperature Operating temperature: 0 ℃ -40 ℃ , storage temperature: -20 ℃ ~60 ℃ Operating Environment Altitude <2000m, relative humidity: %-90%RH(non-condensing), atmospheric pressure: 80-110kPa Net Weight Approx. 9kg Approx. 11kg Dimension 88.0(H)*214.0(W)*398.0(D)mm 88.0(H)*214.0(W)*446.0(D)mm N3410 Series Triple-channel Programmable DC Power Supply...
Page 33
(90%-10%F.S. Variation Time) Voltage Fall Time (full load) 45ms 13ms (90%-10%F.S. Variation Time) Transient Recovery Time ≤1ms Line Regulation-Voltage ≤0.01%+1mV ≤0.01%+3mV Line Regulation-Current ≤0.01%+3mA ≤0.02%+3mA Load Regulation-Voltage ≤0.01%+3mV Load Regulation-Current ≤0.01%+6mA ≤0.02%+3mA Others N3410 Series Triple-channel Programmable DC Power Supply...
Page 34
Altitude <2000m, relative humidity: 5%-90%RH(non-condensing), atmospheric pressure: 80-110kPa Net Weight Approx. 11kg Dimension 2U, 88.0(H)*214.0(W)*446.0(D)mm Note 1: For other specifications, please contact NGI. Note 2: All specifications are subject to change without notice. N3410 Series Triple-channel Programmable DC Power Supply...
Need help?
Do you have a question about the N3410 Series and is the answer not in the manual?