Installation, Operation and Maintenance Instructions
Figure 1. Model 200 Outline Dimensions
You can mount the Model 200 in any position without
affecting its operation. Use the Mounting Bracket,
10311, to mount the booster to any flat surface. For
more information, see Figure 2.
Arrows indicate the Inlet and Outlet ports on the
booster. Tighten all connections securely. Avoid
undersized fittings that will limit the flow through the
booster. For more information, see Figure 1.
Clean all pipelines to remove dirt and scale before
installation.
FAIRCHILD MODEL 200
PNEUMATIC VOLUME BOOSTER
INSTALLATION
Figure 2. Mounting Bracket 10311
Apply a minimum amount of pipe compound to the
male threads of the fitting only. Do Not use teflon
tape as a sealant. Start with the third thread back
and work away from the end of the fitting to avoid
contaminating the booster. Install the booster in the
air line.
NOTE:
Oil free air must be applied to the booster. Use
a filter to remove dirt and entrained liquid in
the air line ahead of the booster. If an air line
lubricator is used, it MUST be located down­
stream of the booster to avoid interference
with performance.
(Sold Separately)

Advertisement

loading

Summary of Contents for Fairchild 200

  • Page 1 Figure 2. Mounting Bracket 10311 (Sold Separately) INSTALLATION You can mount the Model 200 in any position without Apply a minimum amount of pipe compound to the affecting its operation. Use the Mounting Bracket, male threads of the fitting only. Do Not use teflon 10311, to mount the booster to any flat surface.
  • Page 2 Increased Sensitivity Option (L) (Sold Separately) OPERATION INSTALLATION If you have the Model 200 with Increased Sensitivity The Model 200 reproduces a pneumatic signal in a Option (L), use the Mounting Bracket, 19682-1, to 1:1 ratio. Apply pressure to the signal chamber until mount the booster to any flat surface.
  • Page 3 MAINTENANCE To clean the Model 200, use the following steps: 1. Shut off system pressure to the booster to prevent air from escaping. It is not necessary to remove the booster from the air line. 2. Remove the six screws from the bottom of unit. For more information, see Figure 5.
  • Page 4 The information set forth in the foregoing Installation, Operation and Maintenance Instructions shall not be modified or amended in any respect without prior written consent of Fairchild Industrial Products Company. In addition, the information set forth herein shall be furnished with each product sold incorporating Fairchild's unit as a component thereof.