240 bytes APDU length are supported. Using the TP Coupler application, LC100 can be used as KNX TP line coupler to connect different TP lines, but also as a KNX TP area coupler to connect different TP areas or installation systems via a TP Backbone.
- IACK sending on sent out messages is ETS configurable. - When there is no IACK response on the subline, LC100 is able to repeat messages up to three times. Repetitions can be configured for both Physical Telegrams and Group Telegrams via ETS (to ease troubleshooting).
PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 2. Device Technology 2.1. Commissioning Please note for commissioning with default settings: • All telegrams are blocked because the filter table is not defined • The Manual Function switch-off time is 120 min •...
PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 2.2. Device Peripherals 1- Indicator LEDs 2- Function Button 3- Programming LED 4- Programming Button 5- KNX – Main Line 6- KNX – Sub Line Blinked Indicator Green Orange Blinked Red...
PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 2.3. Function Button Long press (3 sec) - Switch to manual override. - Default function is set with LAN line and (KNX) line parameter. - Manual override functionality is configured in “General parameters”.
LED addressing mode Off: normal operating mode On: addressing mode After receiving the physical address, the LC100 automatically returns from addressing mode to the normal operating mode. Button addressing mode Button for switching between normal operating mode and addressing mode for assigning the physical address.
PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 2.5. KNX Topology Via a line/area coupler up to 15 lines can be connected to a main line called an area. It is possible to have up to 64 bus devices on one line. With use of line repeaters, a line can theoretically be extended to 255 bus devices.
LC100 only routes telegrams whose group addresses are entered in its filter table. If a telegram is routed by LC100 without receiving the corresponding acknowledgement, i.e. due to a missing receiver or to a transmission error, the telegram will be repeated up to three times (depending on the ETS setting).
If a telegram is routed by LC100 without receiving the corresponding acknowledgement, i.e. due to a missing receiver or to a transmission error, the telegram will be repeated up to three times (depending on the ETS setting).
PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 3. Default Factory Settings Marking/Design LC100 Physical address 15.15.0 Main Line Group telegrams 0-13 Filter (filter table is empty) Group telegrams 14-31 route all Physical telegrams filter Physical: Repetition if errors on main line...
NOTE: Device default physical address is 15.15.0. In order to configure switch actuator, ETS application file “.knxprod” is needed. It’s possible to download the file on EAE website. ETS is required for programming the device. Parameter settings can be changed by ETS. Learn more by reading ETS help file.
PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 7. ETS Parameters 7.1. General Picture 1: General Range ETS-Text Comment [Default value] disabled pass all telegrams pass all Physical telegrams Configuration setting for telegram routing Manual Function pass all Group telegrams when the Manual Function is active.
Please do not use for normal operation. NOTE: If the parameter “Send confirmation on own telegrams” is set to “yes”, the LC100 systematically sends an ACK on any own routed telegram. Since the repeater does not use a filter table, it is useful to have an ACK sent along with routed telegrams.
PRODUCT MANUAL LC100 EAE KNX LINE COUPLER LC100 R0 7.3. Subline For Group Telegrams and Physical Telegrams the setting “transmit all” is intended only for testing purposes. Please do not use for normal operation. Picture 3: Subline Tab Parameters Range...