PRODUCT MANUAL UD105
EAE KNX UNIVERSAL DIMMER
UD105 R1
EAE KNX UNIVERSAL DIMMER
Product Order Nr: 48038
©
EAE Technology
www.eaetechnology.com
Page 1 / 44

Advertisement

Table of Contents
loading

Summary of Contents for EAE UD105

  • Page 1 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 EAE KNX UNIVERSAL DIMMER Product Order Nr: 48038 © EAE Technology www.eaetechnology.com Page 1 / 44...
  • Page 2: Table Of Contents

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Table of Contents 1.General Features ..................................3 2.Device Technology .................................. 4 2.1 Device Peripherals ................................4 2.2 Connection Diagram ................................ 5 2.3 Technical Data ................................. 6 3. Communication Object Table ..............................7 4.
  • Page 3: General Features

    UD105 R1 1.General Features EAE KNX Universal Dimmer Actuator has 5 independent outputs. Maximum switching voltage is 250V and maximum current is 1 A for each channel. Dimming functions can be used by phase dimming only. The device can be operated manually via push button on it. Each channel can be programmed via ETS4 or above.
  • Page 4: Device Technology

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 2.Device Technology 2.1 Device Peripherals © EAE Technology www.eaetechnology.com Page 4 / 44...
  • Page 5: Connection Diagram

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 2.2 Connection Diagram Single Channel Control Grouped Channel Control © EAE Technology www.eaetechnology.com Page 5 / 44...
  • Page 6: Technical Data

    NOTE: Device default physical address is 15.15.255. In order to configure switch actuator, ETS application file “.knxprod” is needed. It’s possible to download the file on EAE website. ETS is required for programming the device. Parameter settings and related group addresses can be changed by ETS.
  • Page 7: Communication Object Table

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 3. Communication Object Table Number Object Name Function DTP Type Flags of bits General In operation 1.002 1 bit General Scene Control Input 18.001 1 byte 2, 22, 42, 62, 82 Output A…E...
  • Page 8: Priority Order List

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 4. Priority Order List Each function has priority between of them. 1 is highest priority of all. 1- Bus voltage return or failure 2- Forced Operation 3- Permanent ON 4- Staircase Function 5- Brightness or Switch control 5.
  • Page 9 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Button activates Manual Operation On Single Press *On 1s, 1.5s, , 2.5s, 3s Long Press This parameter can be used for selecting Manual Operation activation method of manual button. ▪ Set the parameter to “On Single Press”...
  • Page 10: In Operation

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.1.2 In Operation Enable sending In operation This object is using to report device still alive and connected the KNX bus line. Telegram value is selectable like “0” or “1”. If telegram is not received, device may be defective or KNX cable will be interrupted.
  • Page 11: Telegram Limiting

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Lastly, Channel A or/and Channel B parameters can be taken from Master Channel Parameters for this case. 5.1.4 Telegram Limiting Enable telegram limiting *yes If parameter selected “yes”; Telegram limit count and Telegram limit period duration parameters are visible.
  • Page 12: Master Channel Parameters

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.2 Master Channel Parameters 5.2.1 Master - Dimming Settings Dimming Method *Trailing Edge Dimming Leading Edge Dimming Auto detect based on the load type This parameter is used to select the dimming method based on light load.
  • Page 13: Master - Switching

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 This parameter is used to select minimum dimming level. 5.2.2 Master - Switching Switching On dimming value 0… *100…Last Value This parameter is used to select the dimming level when the relevant output is activated through using Switching object.
  • Page 14: Master - Dimming Control

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.2.3 Master - Dimming Control Dimming time for absolute dimming value input 00:00:00:0…*00:00:03:0…01:49:13:5 (0%...100%) (hh:mm:ss:f) (00:00:00:0 = Instant) This parameter is used to determine the transition timing for absolute dimming action.
  • Page 15: Master - Feedback

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.2.4 Master - Feedback Status Objects Enable switching status object *Yes This parameter is used to show switching status objects. Switching status objects will be visible, If selected “Yes”. Switching status sending mode Don’t transmit...
  • Page 16 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Error Objects Enable comm. object “Overcurrent Error” *checked unchecked This parameter used to show Error Object in case of maximum current limit reaching. Enable comm. object “Overvoltage Error” *checked unchecked This parameter used to show Error Object in case of maximum voltage limit reaching.
  • Page 17 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Measurement Objects Enable comm. object “Current (rms) Measurement” *yes This parameter is used to show the load Current in use for each channel. Load Current value unit is showing as Ampere. (A) Enable cyclic sending of Current (rms) This parameter is used for transmitting the load Current cyclically If selected “yes”.
  • Page 18: Master - Forced Operation

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.2.5 Master - Forced Operation Forced Operation Function *1-bit format 2-bit format This parameter is used to select forced operation activation type. When Forced Operation is activated, any switching, dimming, staircase or scene commands will not affect to the relevant channel.
  • Page 19 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Enable Staircase Warning This parameter is used to enable/disable warning after end of the staircase function. Dimming value during Staircase Warning 0…*50%...100% This parameter is shown when “Enable Staircase Warning: yes” selected. It is used to select dimming value for the relevant channel when device is in Staircase Warning mode.
  • Page 20: Master - Faults

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.2.7 Master - Faults Mains Power Recovery Dimming value after mains power recovery *Status as prior to failure 0…100% This parameter is used to determine the dimming value when the mains power is recovered.
  • Page 21 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 KNX Bus Recovery Dimming value after KNX bus recovery *Don’t change Status as prior to failure 0…100% This parameter is used to determine the dimming value when the KNX Bus recovered.
  • Page 22: Master - Dimming Curve

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.2.8 Master - Dimming Curve Dimming Curve is used for creating the dimming curves customizely. Dimming Section time calculation is shown below. [ �������������� �������������� �� �������� ������������ ] [ �������������� �������������� �� �������� ] = [ �� �������������� �������� ] ×...
  • Page 23 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Dimming Section 1 [0% - th2%] Dimming Section 1 Time Factor *1…255 This parameter defines the dimming section time factor between 0% and th2. “th2” is selected as 25% default. Dimming Section 2 [th2% - th3%] Dimming Section 2 Threshold (th2) 0…*25…100 %...
  • Page 24: Channel A

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.3 Channel A…E 5.3.1 Channel A…E - Dimming Settings Parameter setting *Take over from master Individual This parameter is used to apply parameter settings from master or individually. Dimming Method *Trailing Edge Dimming...
  • Page 25: Channel A

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Maximum dimming percentage 0… *100 This parameter is used to select maximum dimming level. Minimum dimming percentage *0… 100 This parameter is used to select minimum dimming level. 5.3.2 Channel A…E - Switching...
  • Page 26: Channel A

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.3.3 Channel A…E - Dimming Control Parameter setting *Take over from master Individual This parameter is used to apply parameter settings from master or individually. Dimming time for absolute dimming value input 00:00:00:0…*00:00:03:0…01:49:13:5...
  • Page 27: Channel A

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.3.4 Channel A…E - Feedback Parameter setting *Take over from master Individual This parameter is used to apply parameter settings from master or individually. Status Objects Enable switching status object *Yes This parameter is used to show switching status objects.
  • Page 28 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Error Objects Enable comm. object “Overcurrent Error” *checked unchecked This parameter used to show Error Object in case of maximum current limit reaching. Enable comm. object “Overvoltage Error” *checked unchecked This parameter used to show Error Object in case of maximum voltage limit reaching.
  • Page 29 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Measurement Objects Enable comm. object “Current (rms) Measurement” *yes This parameter is used to show the load Current in use for each channel. Load Current value unit is showing as Ampere. (A) Enable cyclic sending of Current (rms) This parameter is used for transmitting the load Current cyclically If selected “yes”.
  • Page 30: Channel A

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.3.5 Channel A…E - Forced Operation Forced Operation function *Disabled Active (1-bit format) Active (2-bit format) Active (Use master parameters) This parameter is used to enable/disable the Forced Operation via getting settings from master parameter or individually.
  • Page 31: Channel A

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.3.6 Channel A…E - Staircase Function Staircase function *Disabled Enabled (Individual parameters) Enabled (Use master parameters) This parameter is used to enable/disable the Staircase function via getting settings from master parameter or individually.
  • Page 32 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Staircase Warning time (hh:mm:ss) 00:00:02…*00:00:05…18:12:15 This parameter is shown when “Enable Staircase Warning: yes” selected. It determines the Staircase Warning time duration. Staircase Warning will be deactivated at the end of the time.
  • Page 33: Channel A

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.3.7 Channel A…E – Faults Parameter setting *Take over from master Individual This parameter is used to apply parameter settings from master or individually. Mains Power Recovery Dimming value after mains power recovery *Status as prior to failure 0…100%...
  • Page 34 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 KNX Bus Recovery Dimming value after KNX bus recovery *Don’t change Status as prior to failure 0…100% This parameter is used to determine the dimming value when the KNX Bus recovered.
  • Page 35: Channel A

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.3.8 Channel A…E - Dimming Curve This parameter tab will be shown, If the Dimming characteristic is selected as “Custom Dimming Curve” in “Dimming Settings”. (see 5.3.1) Parameter setting *Take over from master Individual This parameter is used to apply parameter settings from master or individually.
  • Page 36 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 For an e.g. 2= if it is desired to know the “Dimming Section 3 Time“ while absolute dimming from 0 to 100%. Calculation will be processed with the same parameters in the previous example except “Dimming time for absolute dimming”.
  • Page 37 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Dimming Section 4 [th4% - 100%] Dimming Section 4 Threshold (th4) 0…*75…100 % This parameter is used to select threshold value for th4%. Dimming Section 4 Time Factor *1…255 This parameter defines the dimming time between th4 and 100%.
  • Page 38: Scenes

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 5.4 Scenes The scene function of the switch & dim actuator has an 8-bit scene object. You can define for each 64 scenes with parameter window. Scene can be specified like brightness value and transition time to new brightness.
  • Page 39 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 e.g. Transition time to new brightness= 3 sec Scene Brightness value= % 25 Current Brightness value= % 60 �������������������� �������� ���� ������ ��������ℎ���������� ) × | ���������� ��������ℎ���������� ���������� − �������������� ��������ℎ���������� ���������� | ����������...
  • Page 40: Object Descriptions

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 6. Object Descriptions 6.1 General Object Description Object name Name DTP Type Length Flags In operation General DPT 1.002 1 bit You use this object to report device still alive and contacted the KNX line. Telegram value is select ON/OFF.
  • Page 41 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Object name Name DTP Type Length Flags Switch Output A…E DPT 1.001 1 bit This object is used for switching a triac output ON/OFF. 0: Deactivate the transmission 1: Activate the transmission Status switch Output A…E...
  • Page 42 PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 Object name Name DTP Type Length Flags 1.003 1bit Forced operation Output A...E 2.001 2 bit This object is used to the switching state of the output is directly determined by this object. The first bit is switching state and the second bit is activated or deactivated the forced control.
  • Page 43: Error Objects

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 6.3 Error Objects Object name Name DTP Type Length Flags Overcurrent Error Error Output A…E DPT 1.011 1 bit This object sends the “1” value when the current limit(max 1.8 A) is passed in the related dimming output.
  • Page 44: Measurement Objects

    PRODUCT MANUAL UD105 EAE KNX UNIVERSAL DIMMER UD105 R1 6.4 Measurement Objects Object name Name DTP Type Length Flags Current (rms) Error Output A…E DPT 14.019 4 bytes This object is sending the line current for the related output. Value is showing in Amps ( A ) Voltage (rms) Error Output A…E...