Installation Manual SW108
EAE KNX Switch Actuator 8ch
Connection
1. Physical address label
2. KNX programming key
3. Red KNX programming led
4. KNX connection terminal
5. Switch position display and ON / OFF manual actuation
Description of Device
Device has eight channels which can be configured with ETS3/ETS4 or higher
version. Each channel is independent of one other. It has a separate bistable
switching relay. Also device has manual operating feature. The relay can be
switched on or off with slide switches. There is no feedback to the bus in this case.
The following function list provides;
Staircase
External logic
Internal logic
Priority
Threshold
Operating hour
Sweep
Each channel of devices can choose any of these functions. The outputs are
parameterized individually via ETS3/4 or higher version. After bus voltage failure or
voltage return, relay position is selected by dependence on parameters. In "ETS
reset", device parameters are return download configuration.
Technical Data
Protection Type
IP20
Safety class
II
Power
KNX
Connection
Screw terminals
Max tight torque
KNX
Output
Count
Switching
voltage
Switching
capacity
Fluorescent
lighting load
Output life
Mechanical life
Installation
35 mm
mounting rail
Temperature
Ambient
Storage
Humidity
Max. Humidity
Dimensions
65,5 x 143 x 89mm
Weight
0.30 kg
Box
Plastic, polycarbonate, colour grey
CE
In accordance with the EMC guideline and LV directives
© EAE Technology
Ikitelli Org. San. Bolg. Ziya Gokalp Mah. Eski Turgut Ozal Cad.
No: 20, Zip Code: 34490 Basaksehir/Istanbul Tel: +90 212 549 97 13
EN 60 529
EN 61 140
21V... 30V DC, SELV
0,5...4 mm² solid and stranded wire
0,5...2,5mm² stranded wire with
ferrule
0.8 Nm
Bus connection terminal
8
277/440V AC; 50/60 Hz
277 V AC 16A / AC 1
EN60 669-1 16 AX/250 VAC
> 3 x 10
6
EN 60 715
-5° C + 45° C
-25° C + 55° C
95 % non condense
www.eaetechnology.com
Operation and Display
-Display of switch position
(5)
-On/Off manual operation
The contact position shows the current situation of load circuit. It can be changed
manually ON and OFF position.
-Programming Led
(3)
Red led lights up after the programming button is pressed.
Installation
The device is compatible for mounting to 35 mm DIN rail EN 60 715.
Connection
KNX connector must be connected to the KNX connection terminal. Ensure that
colour of cables are connected accurate. Load connections are made using screw
terminals. Different phase lines can be connected to load channels at the same
time. (L1, L2, L3)
Commissioning
Determination of the physical address and setting of parameters are actualized
with Engineering Tool Software (ETS3/ETS4 or higher). ".knxprod" file must be
imported to the ETS. Please check website for latest ".knxprod" file.
www.eaetechnology.com
A detailed information about parameter configuration can be found in
Product Manual of device.
Installation and commissioning of device may only be implemented by trained
electricians. The relevant standards, directives, regulations and instructions must
be observed when planning and implementing the electrical installation.
-When connecting the device make sure that the device is isolated!
-Protect the device against moisture, dirt and damage during transport, storage
and operation!
-Do not operate the device out of the specified technical data which is stated.
-The device may only be operated in closed enclosures (Distribution boards etc.)
Cleaning
If device becomes dirty, only a dry cloth can be used for cleaning. It is not suitable
to use wet cloths, caustics and solvents.
SW108 IM R2.0
Scale Drawing

Advertisement

loading

Summary of Contents for EAE SW108

  • Page 1 Installation Manual SW108 EAE KNX Switch Actuator 8ch SW108 IM R2.0 Operation and Display -Display of switch position -On/Off manual operation The contact position shows the current situation of load circuit. It can be changed manually ON and OFF position.
  • Page 2 Installation Manual SW104 EAE KNX Switch Actuator 4ch SW104 R1.0 Operation and Display -Display of switch position -On/Off manual operation The contact position shows the current situation of load circuit. It can be changed manually ON and OFF position. -Programming Led Red led lights up after the programming button is pressed.