SF-200 January 5, 2021 SureFire II Pilot Forced Draught Gas Pilot type SP- 32-NG/PG-FD Instruction Manual INTRODUCTION This Instruction Manual contains a description of the type SP-32-NG/PG-FD gas pilot construction, SureFire IITM operation principle and the instructions for installation, start-up and service, including the industrial health & safety recommendations.
Page 2
The orifice-stabilizer assembly is optimized for Natural gas or Propane gas/LPG. In case of other Fuel gas type or other capacity needed, contact Fireye as this may need the pilot construction changes - see p. 11 for Special Pilots.
Page 3
3. MOUNTING TUBES For fixing the pilot burner to a burner plate there are two types of mounting tubes available (material: carbon steel), offered as an optional accessory and to be ordered separately (see Fig. 2): a flange mounting tube allowing the fixing of a gas pilot without the use of welding, to be fixed with bolts to the burner plate.
304/316 SS and heat-resistant steel 310/330 SS Notes: 1. If the above parameters are different than those required please contact Fireye 2. For Imperial Units please refer to the Appendix 4 Unit Conversion Table 3. Device complies with the requirements of the European Directive 2011/65/EU (RoHS 2)
WARNING: ALL ACTIONS RELATED TO THE INSTALLATION, SERVICE AND OPERATION OF GAS PILOT MAY ONLY BE CARRIED OUT BY A TRAINED AND QUALIFIED PERSONNEL. REMARK: IN CASE OF ANY DOUBTS REGARDING INSTALLATION OF THE PILOT CONSULT WITH THE MANUFACTURER. INSTALLATION During the installation, all components have to be protected from impact or bending.
Page 6
It should be remembered that the rod tip positioning against the stabilizer plate in the pilot gas part assembly (pos. 3 on Fig.1) should be done outside the air tube only. Only after proper rod positioning should the rod be fixed by tightening the gland and the whole gas assembly with rod inserted into the air tube.
Page 7
REMARK: AT THE DESIGN STAGE DETERMINE LENGTH OF CABLES AND FLEXIBLE AIR AND GAS CONNECTIONS TO ACCOMMODATE ANY EXPECTED HEATER OR BOILER CONSTRUCTION MOVEMENT PILOT START-UP, OPERATIONAL TESTS Before proceeding with the start-up and operational tests of SP-32-NG/PG-FD pilot check the following: 8.1 Gas and air installations are correctly mounted, tight and functionally checked, including: valves, flaps, strainers, fittings and joints (flanged and screwed), control and interlock devices.
OPERATION After installing and completion of pilot start up and tests SP-32-NG/PG-FD is ready for operation. General description of activities performed by the burner/boiler control system or manually by the operator: 9.1 Preparation of the furnace/boiler for firing up. 9.2 Opening of air to the burner and pilot. 9.3 Preparation of gas installation for operation.
10.1 INSPECTION AND MAINTENANCE SP-32-NG/PG-FD pilot because of its simple design does not require complicated maintenance procedures. Checking and cleaning of gas tube and orifice-stabilizer assembly: Close the manual gas valve and disconnect the pilot gas line. Disconnect the ignition rod electric supply cable. Unscrew the locking screw and the mounting ring.
Page 10
11.2 In case of air tube wear or damage: if air tube or mounting ring has to be replaced - order a replacement air tube (with mounting ring) of length – “L” – prices on request only, if just the end of air tube is eroded by temperature - cut 200 mm of the tube tip and weld new section of the – ...
Part Number in such case is SP-32-ZYY-F-xxx where: “ Z ” is capacity range e.g. S-small, M-medium, L-large or possibly others, “ YY ” is the specific Project Number given by Fireye after analyzing the Proposal Data Sheet, “ F ” is Forced draught, “...
Page 13
APPENDIX No 2 Proper position of the SureFire II™ SP-32 and SP-48 Pilots on burners Appendix shows a sample of typical positions of gas pilots on two types of burners. Gas Igniter operating as an intermittent (light-off) on a sample single gun main burner, oil or gas fired, vertical or horizontal mounting.
Page 14
APPENDIX No 3 Proposal Data Sheet SureFire II Pilot - Forced Draught Gas Pilot Type SP-32-NG/PG-FD-xxx Please provide the following data before placing the Order for gas pilot: Information about End User — Plant Name: — Owner: — Country: — Localization (address): Gas pilot mode of operation: — ...
APPENDIX No 4 UNIT CONVERSION TABLE Quantity Metric Units Imperial Units Length 1 millimeter [mm] x 0.003281 = foot [ft.; ’] x 0.03937 = inch [in; ”] 1 meter [m] x 3.281 = foot [ft; ’] x 39.370 = inch [in; ”] Volume 1 cubic meter [m x 35.315 = cubic foot [ft...
Page 16
Fireye warranty, as stated in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance.
Need help?
Do you have a question about the SureFire II SP32-NG-FD and is the answer not in the manual?
Questions and answers