1.
INTRODUCTION
This Instruction Manual contains a description of the type
operation principle and the instructions for installation, start-up and service, including the industrial health & safety
recommendations.
The SP-32-NG/PG-FD (32 mm outer diameter, NG - Natural Gas or PG - Propane Gas or LPG, FD - forced draught)
gas pilot is a reliable and effective source of ignition for oil and gas burners.
Pilot Part Number for Natural Gas is "SP-48-NG-FD-xxx", for Propane Gas or LPG gas is "SP-48-PG-FD-xxx"
where "-xxx" is the insertion length "L" from 0.5 to 3.0 metres. (see Appendix 1 – the pilot capacity vs. gas pressure
graphs for Natural gas and Propane). For other Fuel gas types or capacity ranges – see p. 11 Ordering Information for
Special Pilots Part Numbering approach.
The pilot is constructed of high quality materials and each unit is checked and tested before dispatch.
Acquaintance with the following instructions and strict attention to the indications reduce the possibility of equipment
failure to a minimum and ensure safety during normal operation.
FIGURE 1.
Gas pilot type SP-32-NG/PG-FD.
© 2021 Carrier
SureFire II
Forced Draught
Gas Pilot type SP-
32-NG/PG-FD
Instruction Manual
SP-32-NG/PG-FD gas pilot construction,
SureFire IITM
SF-200
January 5, 2021
TM
Pilot
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the SureFire II SP32-NG-FD and is the answer not in the manual?

Questions and answers

Summary of Contents for Fireye SureFire II SP32-NG-FD

  • Page 1 SF-200 January 5, 2021 SureFire II Pilot Forced Draught Gas Pilot type SP- 32-NG/PG-FD Instruction Manual INTRODUCTION This Instruction Manual contains a description of the type SP-32-NG/PG-FD gas pilot construction, SureFire IITM operation principle and the instructions for installation, start-up and service, including the industrial health & safety recommendations.
  • Page 2 The orifice-stabilizer assembly is optimized for Natural gas or Propane gas/LPG. In case of other Fuel gas type or other capacity needed, contact Fireye as this may need the pilot construction changes - see p. 11 for Special Pilots.
  • Page 3 3. MOUNTING TUBES For fixing the pilot burner to a burner plate there are two types of mounting tubes available (material: carbon steel), offered as an optional accessory and to be ordered separately (see Fig. 2): a flange mounting tube allowing the fixing of a gas pilot without the use of welding, to be fixed with bolts to the burner plate.
  • Page 4: Technical Data

    304/316 SS and heat-resistant steel 310/330 SS Notes: 1. If the above parameters are different than those required please contact Fireye 2. For Imperial Units please refer to the Appendix 4 Unit Conversion Table 3. Device complies with the requirements of the European Directive 2011/65/EU (RoHS 2)
  • Page 5: Appendix 2 Should Be Strictly Observed

    WARNING: ALL ACTIONS RELATED TO THE INSTALLATION, SERVICE AND OPERATION OF GAS PILOT MAY ONLY BE CARRIED OUT BY A TRAINED AND QUALIFIED PERSONNEL. REMARK: IN CASE OF ANY DOUBTS REGARDING INSTALLATION OF THE PILOT CONSULT WITH THE MANUFACTURER. INSTALLATION During the installation, all components have to be protected from impact or bending.
  • Page 6 It should be remembered that the rod tip positioning against the stabilizer plate in the pilot gas part assembly (pos. 3 on Fig.1) should be done outside the air tube only. Only after proper rod positioning should the rod be fixed by tightening the gland and the whole gas assembly with rod inserted into the air tube.
  • Page 7 REMARK: AT THE DESIGN STAGE DETERMINE LENGTH OF CABLES AND FLEXIBLE AIR AND GAS CONNECTIONS TO ACCOMMODATE ANY EXPECTED HEATER OR BOILER CONSTRUCTION MOVEMENT PILOT START-UP, OPERATIONAL TESTS Before proceeding with the start-up and operational tests of SP-32-NG/PG-FD pilot check the following: 8.1 Gas and air installations are correctly mounted, tight and functionally checked, including: valves, flaps, strainers, fittings and joints (flanged and screwed), control and interlock devices.
  • Page 8: Operation

    OPERATION After installing and completion of pilot start up and tests SP-32-NG/PG-FD is ready for operation. General description of activities performed by the burner/boiler control system or manually by the operator: 9.1 Preparation of the furnace/boiler for firing up. 9.2 Opening of air to the burner and pilot. 9.3 Preparation of gas installation for operation.
  • Page 9: Inspection And Maintenance

    10.1 INSPECTION AND MAINTENANCE SP-32-NG/PG-FD pilot because of its simple design does not require complicated maintenance procedures. Checking and cleaning of gas tube and orifice-stabilizer assembly: Close the manual gas valve and disconnect the pilot gas line. Disconnect the ignition rod electric supply cable. Unscrew the locking screw and the mounting ring.
  • Page 10 11.2 In case of air tube wear or damage: if air tube or mounting ring has to be replaced - order a replacement air tube (with mounting ring) of length –  “L” – prices on request only, if just the end of air tube is eroded by temperature - cut 200 mm of the tube tip and weld new section of the – ...
  • Page 11: Ordering Information

    Part Number in such case is SP-32-ZYY-F-xxx where: “ Z ” is capacity range e.g. S-small, M-medium, L-large or possibly others, “ YY ” is the specific Project Number given by Fireye after analyzing the Proposal Data Sheet, “ F ” is Forced draught, “...
  • Page 12 APPENDIX No 1 The Pilot capacity vs. gas pressure graphs – standard version Remark: The real measured capacity may differ by ± 5% depending on a particular pilot and measurement conditions © 2021 Carrier...
  • Page 13 APPENDIX No 2 Proper position of the SureFire II™ SP-32 and SP-48 Pilots on burners Appendix shows a sample of typical positions of gas pilots on two types of burners. Gas Igniter operating as an intermittent (light-off) on a sample single gun main burner, oil or gas fired, vertical or horizontal mounting.
  • Page 14 APPENDIX No 3 Proposal Data Sheet SureFire II Pilot - Forced Draught Gas Pilot Type SP-32-NG/PG-FD-xxx Please provide the following data before placing the Order for gas pilot: Information about End User —  Plant Name: —  Owner: —  Country: —  Localization (address): Gas pilot mode of operation: — ...
  • Page 15: Unit Conversion Table

    APPENDIX No 4 UNIT CONVERSION TABLE Quantity Metric Units Imperial Units Length 1 millimeter [mm] x 0.003281 = foot [ft.; ’] x 0.03937 = inch [in; ”] 1 meter [m] x 3.281 = foot [ft; ’] x 39.370 = inch [in; ”] Volume 1 cubic meter [m x 35.315 = cubic foot [ft...
  • Page 16 Fireye warranty, as stated in its General Terms and Conditions of Sale, pertains only to the Fireye products and not to any other equipment or to the combined system or its overall performance.

This manual is also suitable for:

Surefire ii sp32-pg-fd

Table of Contents