S-plan Wiring
PAW cylinders can be
fitted with all types of boilers and heat
pumps operating using room and
cylinder thermostats.
Please follow upper diagram:
'Wiring for Standard Heat Pump'.
Thermistor controlled Heat
Pumps/Boilers
Many popular Heat Pumps now
use a thermistor principle. A
thermistor temperature sensor is
supplied with the Heat Pump to
attach to the cylinder.
Temperature information is
relayed back to the Heat Pump
control system.
A Pocket is provided (see below
to secure the sensor on the
PAW cylinder. The
probe is run through a channel
from base of cylinder to the
immersion housing and housed
there in a pocket. The thermistor
cable should be secured using
the supplied clamps in the bottom
opening of the channel. A
motorised valve must be used in
accordance with Building
Regulation G3. This is wired from
the additional cylinder
thermostat, wired as high limit
stat. Please follow lower diagram:
'Wiring for Thermistor Controlled
Heat Pump"
Channel running
from base of cylinder
Using Additional Cylinder Thermostat
as high limit stat only:
- coil the grey temperature
probe wire inside additional
cylinder thermostat box and insert
black probe into thermostat pocket
of cylinder then turn dial on front to
number 5
Wiring for Standard Heat pump
Zone Valve (Htg)
(not supplied)
V4043H
G
Br B1 O
G/Y
1
2
3
Isolated Mains
L N E
Supply From
1 2
3
Fused Spur
1 2 3
L N E 4
3
HTG
HW
ST6400
ON
ON
Programmer
Wiring for Thermistor Controlled Heat Pump
Zone Valve (Htg)
(not supplied)
V4043H
G
Br
B1 O
G/Y
1
2
3
Isolated Mains
L N E
Supply From
1 2
3
Fused Spur
1 2 3
L N E 4
3
HTG
HW
ST6400
ON
ON
Programmer
Piping
Diagram
HP/Boiler
Cylinder
Room
Thermostat
thermostat
(supplied)
T6360B
N
C NC NO
1
3
2
1 2
2
4
5
6
7
8
2 3
L N E
Heat Pump
Cylinder
Thermostat
Room
(supplied) Wired as
thermostat
high limit stat
N
C NC NO
T6360B
1
3
2
1 2
2
4
5
6
7
8
2 3
L N E
Heat pump differential controler
2-port valve
Zone valve
(supplied)
(not supplied)
Automatic
bypass
Pump
flow
Zone Valve (DHW)
(supplied)
V4043H
G Br Bl
O
G/Y
1
2
3
10
9
2 3
L N E
Pump
Zone Valve (DHW)
(supplied)
V4043H
G Br Bl
O
G/Y
1
2
3
Thermistor wire
9
10
Connected to
Heat Pump control
system
2 3
L N E
Pump
Radiators/
UFH
7