Nordyne NS6BD Series User's Manual & Installation Instructions page 18

Split system air conditioner
Table of Contents

Advertisement

600
575
550
525
Remove refrigerant when above curve
500
475
450
425
400
375
350
325
300
275
250
75
80
NOTE: Do not add or remove refrigerant if pressure reading is between the curves.
600
575
550
525
500
475
450
425
400
375
350
325
300
275
250
75
18
S6BD048K TXV Charging Chart
85
90
95
Figure 11. Charging Chart for 4 Ton Units
S6BD060K TXV Charging Chart
Remove refrigerant when above curve
80
85
90
95
Figure 12. Charging Chart for 5 Ton Units
100
105
110
Liquid Temperature ( ° F)
Add refrigerant when below curve
100
105
110
Liquid Temperature ( ° F)
Add refrigerant when below curve
115
120
125
115
120
125
130
130
135
135