Download Print this page

Delta DOP-103SQ Instruction Sheet page 2

Advertisement

Available languages
  • EN

Available languages

Wiring:
Type
Wire gauge (AWG)
Stripped length
Solid
24 - 12
7 - 8 mm (0.28 - 0.31 inches)
Stranded
24 - 12
7 - 8 mm (0.28 - 0.31 inches)
Refer to the following diagram for wiring the power connector.
The temperature rating of the cable must be greater than 75°C (167°F).
Reportez-vous au schéma suivant pour le câblage du connecteur d'alimentation. La
température nominale du câble doit être supérieure à 75°C (167°F).
(6) Hardware specifications
Model
DOP-103SQ
Panel type
4.3" TFT LCD (65,535 colors)
Resolution
480 x 272 pixels
Backlight
LED backlight (half-life at room temperature of 25°C (77°F) > 20,000 hours)
Display range
95.04 x 53.856 mm
Brightness
400 cd/m² (Typ.)
CPU
ARM Cortex-A8 (800 MHz)
Flash ROM
256 Mbytes
RAM
256 Mbytes
Touchscreen
4-wire resistive touchscreen > 1,000,000 operated
Buzzer
Multi-tone frequency (2 - 4 kHz) / 80 dB
Network interface
USB
1 USB slave Ver 2.0; 1 USB host Ver 2.0
SD
COM1
RS-232 (supports flow control) / RS-485
COM2
RS-422 / RS-485
COM3
Auxiliary function key
Calendar
Built-in
Cooling method
Natural cooling
CE / UL
Approvals
(use shielded network cable and magnetic ring with the filter of 300 ohm / 100 MHz)
Panel waterproof level
IP65 / NEMA4 / UL TYPE 4X (for indoor use only)
DC +24V (-15% to +15%) (use an isolated power supply)
Operation voltage
*2
Supplied by Class 2 or SELV circuit (isolated from MAINS by double insulation)
Dielectric strength
500 V
for 1 minute (between DC24V terminal and FG terminal)
AC
Power consumption
*2
5.67 W (Max.)
Backup battery
3V lithium battery (CR2032) × 1
About 3 years or more at room temperature of 25°C (77°F)
Backup battery life
(subject to operating temperature and condition)
Operating temperature
0°C to 50°C (32°F to 122°F)
Storage temperature
-20°C to +60°C (-4°F to +140°F)
Model
Torque
Operating environment
5 kg-cm (4.3 lb-in)
5 kg-cm (4.3 lb-in)
Vibration resistance
Shock resistance
Dimensions
(W) x (H) x (D) mm
Mounting dimensions
(W) x (H) mm
Weight
Note:
1.
The half-life of the backlight is defined as the maximum luminance being reduced by 50% when the maximum drive current is supplied
to the HMI. The life of LED backlight specified here is estimated at room temperature of 25°C (77°F) with ambient humidity.
2.
The withstand voltage of the isolated power circuit is 1500V peak for 1 minute.
3.
The HMI power consumption is the power consumed when the HMI is not connecting with other peripheral devices. To ensure normal
operation of the HMI, the recommended capacity of the power supply is 1.5 to 2 times of the specified power consumption.
4.
Isolated power supply is recommended.
5.
To download the DOP-100 series programming software DOPSoft and the user manual, go to Delta's website at http://www.deltaww.com.
6.
The DOP-100 series can be used with other industrial automation equipment. Read this sheet carefully and install the product
according to the instructions to avoid danger.
*1
N/A
N/A
*2
*2
N/A
N/A
*3
DOP-103SQ
10% to 90% RH [0°C to 40°C (32°F to 104°F)]
10% to 55% RH [41°C to 50°C (105.8°F to 122°F)]
Pollution degree: 2
Conforms to IEC61131-2: continuous vibration 5 Hz - 8.3 Hz with amplitude
3.5 mm; 8.3 Hz - 150 Hz with amplitude 1G
Conforms to IEC60068-2-27: 11 ms, 15 G Peak,
in X, Y, Z directions each for 6 times
129 x 103 x 37.8
118.8 x 92.8
Approx. 280 g

Advertisement

loading