Download Print this page
Intermatic T100 Series Instruction Sheet

Intermatic T100 Series Instruction Sheet

24 hour dial time switch mechanisms

Advertisement

Available languages

Available languages

Quick Links

WARNING
Risk of Fire or Electric Shock
• Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing.
• Installation and/or wiring must be in accordance with national and local electrical code requirements.
• Use wires rated at least 90°C - COPPER conductors ONLY.
• Replace plastic insulator covering terminals before powering ON.
• KEEP DOOR CLOSED AT ALL TIMES when not servicing.
NOTICE
NOTICE
• Rotate timer dial clockwise only.
• Do not move the clock hands on the timer. Moving the clock hands can damage the timer.
Load Ratings:
T101M/T103M/T106M:
40 A RESISTIVE, INDUCTIVE, TUNGSTEN
OR 1000 VA PILOT DUTY 120/208/240 VAC;
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
16 A ELECTRONIC BALLAST, 277 VAC
T104M:
40 A RESISTIVE EACH POLE, 120-480 VAC
40 A INDUCTIVE, TUNGSTEN OR 1000 VA
PILOT DUTY EACH POLE 120V-277 VAC;
2 HP (24 FLA) - 120 VAC; 5 HP (28 FLA) - 240 VAC
16 A ELECTRONIC BALLAST, 277 VAC
Wiring Diagrams:
T101M: SINGLE POLE SINGLE THROW (SPST)
CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
ON
DIAL
TRIPPER
TIME
POINTER
OFF
TRIPPER
MANUAL
LEVER
T103M: DOUBLE POLE SINGLE THROW (DPST)
CLOCK MOTOR: 120 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
ON
TRIPPER
DIAL
TIME
POINTER
OFF
TRIPPER
MANUAL
LEVER
Wiring Instructions: Remove 1/2 inch of insulation from wire ends. Tighten terminal screws firmly (2-18 in-lbs).
Use solid or stranded COPPER conductors only. May use two wires of the same size and type.
MAX.
MIN.
MINIMUM
75°C INSULATION MAX. MOTOR
INSUL-
COPPER
LOAD
LOAD (HP)
(AMP)
ATION
WIRE SIZE
3 PHASE
SINGLE PHASE
TEMP(°C)
(AWG)
120 V.
240 V.
208 V.
14
90
1/2
2
15
12
20
90
1
2 1/2
N/A
3
10
30
90
2
8
5
40
90
-
Programming Instructions:
1.
TO SET "ON" AND "OFF" TIMES: Hold trippers against edge of CLOCK-DIAL, pointing to time (AM or PM) when ON and OFF
operations are desired, tighten tripper screws firmly. For additional tripper pairs on CLOCK-DIAL order 156T1978A.
2.
TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in either direction and align the exact time-of-day on the CLOCK-DIAL
(the time now, when switch is being put into operation) to the pointer. DO NOT MOVE POINTER.
Operating Instructions:
TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER below CLOCK-DIAL left or right as indicated by arrows. This will not
effect next operation.
IN CASE OF POWER FAILURE, reset CLOCK-DIAL to proper time-of-day. See programming instructions.
WIRING
DIAGRAM
GRD.
A
1
2
120V
NEUT.
SUPPLY
LINE
GROUND
TYPICAL
WIRING
DIAGRAM
A
1
2
3
4
120/240
NEUT.
VOLT
LINE 1
3 WIRE
SUPPLY
LINE 2
GROUND
GR.
PRESSURE PLATE
TERMINAL SCREW
240 V.
MAKE SURE WIRE
N/A
INSULATION CLEARS
PRESSURE PLATE
T100 SERIES MECHANISM INSTRUCTION SHEET
24 Hour Dial Time Switch Mechanisms
T104M: DOUBLE POLE SINGLE THROW (DPST)
CLOCK MOTOR: 208-277 VAC, 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
TIME
CLOCK
DIAL
MOTOR
TIME
POINTER
OFF
TO
TRIPPER
LOAD
MANUAL
LEVER
T106M:
ONE NORMALLY OPEN, ONE NORMALLY CLOSED CONTACTS - (CAN BE WIRED AS SPDT)
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE PART NO. (WG--) ON MOTOR COVER.
CLOCK
DIAL
CLOCK
TIME
MOTOR
POINTER
OFF
TRIPPER
MANUAL
TO
LEVER
LOADS
WIRING INSTRUCTIONS: To wire switch follow diagram above. To wire as SINGLE POLE
NORMALLY CLOSED, move clock motor lead from terminal 3 to 1, and connect LINE to 1,
LOAD to 2. To wire as SINGLE POLE DOUBLE THROW, install jumper (the same gauge
as line wire) between 2 and 3 and connect LINE to 2, LOADS to 1 and 4. NOTE: Line 2 if
present is uninterrupted.
WIRING
DIAGRAM
ON
240 V 2 WIRE
TRIPPER
AND GROUND
A
GR
LINE 1
240V
LINE 2
SUPPLY
277/480 VOLT CONNECT MOTOR LEADS TO TERMINALS
"A" AND 1 AND SUPPLY NEUTRAL TO TERMINAL "A".
CLOCK MOTOR: 208-277 VAC, 60 HZ.
ON
TRIPPER
CLOCK
MOTOR
FROM
GRD
208V
A
240V
N
OR
277V
LINE
SUPPLY
FIGURE 1
TYPICAL WIRING SINGLE POLE NORMALLY OPEN
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
CLOCK
MOTOR
1
2
3
4
TO
LOAD(S)
GROUND
WIRING DIAGRAM
1
2
3
4
TO
LOAD
GROUND

Advertisement

loading

Summary of Contents for Intermatic T100 Series

  • Page 1 T100 SERIES MECHANISM INSTRUCTION SHEET 24 Hour Dial Time Switch Mechanisms WARNING Risk of Fire or Electric Shock • Disconnect power at the circuit breaker(s) or disconnect switch(es) before installing or servicing. • Installation and/or wiring must be in accordance with national and local electrical code requirements.
  • Page 2 FICHE D’INSTRUCTION DES MÉCANISMES SÉRIE T100 Mécanismes de minuterie à cadran 24 heures AVERTISSEMENT Risque d’incendie ou de choc électrique • Débrancher l’alimentation au niveau des disjoncteurs ou des sectionneurs avant de procéder à l’installation ou à l’entretien. • L’installation et/ou le câblage doivent être conformes aux exigences du code de l’électricité...
  • Page 3 HOJA DE INSTRUCCIONES DEL MECANISMO SERIE T100 Mecanismos de interruptor temporizador con dial de 24 horas ADVERTENCIA Riesgo de incendio o descarga eléctrica • Desconecte la energía desde los disyuntores o los interruptores de desconexión antes de realizar la instalación o el mantenimiento. •...
  • Page 4 INTERMATIC INCORPORATED Libertyville, Illinois 60048 U.S.A. www.intermatic.com 158--02138...

This manual is also suitable for:

T101mT103mT106mT104m