Intermatic T106R Supplementary Manual
Intermatic T106R Supplementary Manual

Intermatic T106R Supplementary Manual

24 hour dial time switch

Advertisement

Quick Links

158TS10916
10/31/03
MODEL: T106R
24 HOUR DIAL TIME SWITCH
IN TYPE 3R RAINPROOF ENCLOSURE SUITABLE FOR POOL
EQUIPMENT CONTROL IF INSTALLED 5 FT. OR MORE FROM EDGE OF POOL
ONE NORMALLY OPEN - ONE NORMALLY CLOSED CONTACTS
MAY BE WIRED AS SINGLE POLE DOUBLE THROW.
40 AMP. RESISTIVE INDUCTIVE, TUNGSTEN OR
1000 VA PILOT DUTY 120-277 VOLT AC;
2 HP (24 FLA)-120V AC; 5 HP (28 FLA)-240V AC.
CLOCK MOTOR: 208-277 VOLTS - 60 HZ.
CLOCK MOTOR VOLTAGE AND CYCLE MUST BE AS SPECIFIED. TO
ORDER REPLACEMENT, INDICATE ART NO. (WG--) ON MOTOR COVER.
CLOCK
DIAL
TIME
POINTER
OFF
TRIPPER
MANUAL
LEVER
WIRING INSTRUCTIONS: To wire switch follow diagram above. To wire
as SINGLE POLE NORMALLY CLOSED, move motor lead from terminal
3 to 1, and connect LINE to 1, LOAD to 2. To wire as SINGLE POLE
DOUBLE THROW, install jumper (the same gauge as LINE wire)
between terminals 2 and 3 and connect LINE to 2, LOADS to 1 and 4.
NOTE: Line 2 if present is uninterrupted. Use COPPER wire only. For
gauge selection and wire connection, see details below. Use 3/16 or
larger screwdriver to tighten terminal screws firmly. (25 lb-in minimum).
REPLACE INSULATOR BEFORE TURNING ON ELECTRICITY.
MIN.
MINIMUM
MAX.
INSUL-
LOAD
COPPER
(AMP)
ATION
WIRE SIZE
TEMP(°C)
(AWG)
14
60
15
12
60
20
10
30
60
8
40
75
PROGRAMMING INSTRUCTIONS
1. TO SET "ON" AND "OFF" TIMES: Hold trippers against edge
of CLOCK-DIAL, pointing to time (AM or PM) when ON and
OFF operations are desired, tighten tripper screws firmly. For
additional tripper pairs on CLOCK-DIAL order 156T1978A.
2. TO SET TIME-OF-DAY: Pull CLOCK-DIAL outward. Turn in
either direction and align the exact time-of-day on the CLOCK-
DIAL (the time now, when switch is being put into operation) to
the pointer. DO NOT MOVE POINTER.
OPERATING INSTRUCTIONS
• TO OPERATE SWITCH MANUALLY: Move MANUAL LEVER
below CLOCK-DIAL left or right as indicated by arrows. This
will not effect next operation.
• IN CASE OF POWER FAILURE, reset
proper time-of-day. See programming instructions.
INTERMATIC INCORPORATED
SPRING GROVE, ILLINOIS 60081-9698
158TS10916
10:06 AM
ON
TRIPPER
FROM
208V,
240V
OR
277V
SUPPLY
TYPICAL WIRING SINGLE POLE NORMALLY OPEN
SEE WIRING INSTRUCTIONS BELOW FOR OTHER TYPES
75°C INSULATION MAX. MOTOR
LOAD (HP)
3 PHASE
SINGLE PHASE
120 V.
240 V.
208 V.
240 V.
1/2
2
1
2 1/2
N/A
N/A
3
2
5
-
Page 1
CLOCK
MOTOR
GRD
A
2
1
LINE
PRESSURE PLATE
TERMINAL SCREW
MAKE SURE WIRE
INSULATION CLEARS
PRESSURE PLATE
CLOCK-DIAL to
LR3730
WIRING DIAGRAM
3
4
TO
LOAD
GROUND