Input Registers; Holding Registers - Lochinvar ARMOR 101 Series Instructions Manual

Modbus and bacnet communication
Hide thumbs Also See for ARMOR 101 Series:
Table of Contents

Advertisement

5
BACnet Memory Map
Memory Map
(continued)
Object Name
Binary Inputs 0-15
Binary Inputs 16-31
Binary Inputs 32-47
System / Cascade Setpoint
Cascade Total Power
Cascade Current Power
Outlet Temperature
Inlet Temperature
Flue Temperature
Firing Rate
Status Code
Blocking Code
Lockout Code
Binary Inputs 48-63
Lock-Out Error Leader
Lock-Out Error Member 1
Lock-Out Error Member 2
Lock-Out Error Member 3
Lock-Out Error Member 4
Lock-Out Error Member 5
Lock-Out Error Member 6
Lock-Out Error Member 7
Confi guration
0-10 Volt Input / Rate Command / Setpoint Command
Tank Setpoint
Tank Temperature
12
Coils
Object
Object
Type
Instance
Inputs
AI
0
AI
1
AI
2
AI
3
AI
5
AI
6
AI
8
AI
9
AI
10
AI
11
AI
13
AI
14
AI
15
AI
25
AI
26
AI
27
AI
28
AI
29
AI
30
AI
31
AI
32
AI
33
Analog Values
AI
0
AI
1
AI
2
AI
3
AI
4
ModBus and BACnet Instructions
Units
Min
Max
none
0
65535
none
0
65535
none
0
65535
Deg. C
0
130
Percent
100
800
Percent
0
800
Deg C
0
130
Deg C
-20
130
Deg C
-20
130
Percent
0
100
none
0
65535
none
0
65535
none
0
65535
none
0
65535
none
0
1
none
0
1
none
0
1
none
0
1
none
0
1
none
0
1
none
0
1
none
0
1
none
0
65535
none
0
65535
Percent
0
100
Deg C
0
87,5
Deg C
-20
130
Resolution
1
1
1
0.5
1
1
0,1
0,1
0,1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0,5
0,1