UVL-FCU ULTRAVIOLET LAMP KITS FOR FAN COIL AND PTAC UNITS
CAUTION
Breakable Glass Hazard.
Can cause personal injury.
Be careful when inserting bulb(s) into lamp base.
Wear protective gloves when handling bulb(s).

MERCURY NOTICE

This device contains mercury in the sealed
ultraviolet bulb(s). Do not place your used bulb(s)
in the trash. Dispose of properly.
Broken Bulb Cleanup.
Do not use a household vacuum. Sweep debris into a
plastic bag and dispose of properly.
Contact your local waste management authority for
instructions regarding recycling and the proper disposal
of old bulb(s).

Power Supply Installation

IMPORTANT
The UVL-FCU components are designed to with-
stand the typical ambient temperatures found
near fan coil and PTAC heating elements up to a
constant 194°F (90°C). If installing the lamp near
a heating element, secure the wires as far away
from the heating elements' wires as possible to
prevent them from touching the element. In addi-
tion, use the included slit loom tubing for addi-
tional protection of the power supply wires that
may be mounted near the heating elements.
Find a suitable location for the power supply inside the
control panel of the air handler. Install using the self-
tapping screws.
24 VAC
18 - 32 VAC Power Supply
110 - 277 VAC Power Supply
Fig. 5. Power Supply Installation
31-00403—02

Sight Glass Installation

Sight glass may not be needed if reflected UV light is
visible.
1. Find a suitable location on the outside of the unit
near the UV lamp installation and apply the warn-
ing/lamp replacement sticker.
2. Drill a ½ inch hole through the orange circle on the
sticker. Press the UV safety viewport into the hole.
3. When power is connected the sight glass can be
used to confirm the UV lamp is operating.
Fig. 6. Sight Glass Installation
WIRING
WARNING
Electric Shock Hazard.
Can cause personal injury.
Turn off main power before making electrical
connections.
IMPORTANT
Check which power supply is included with your
UVL-FCU kit before connecting to power.
Use the wiring diagrams below (Fig. 7) to connect to
power. The low voltage power supply (18 to 32 VAC) is
marked "LOW". The high voltage (120 to 277 VAC) power
supply is marked "LINE".