Page 1
Dip Switch Settings Variations for Hydronic (Water Cooled) Page 14 This is a Quick Reference document covering the features and functions of the UC7 along with connectivity details and fault diagnosis troubleshooting information. For more detailed information regarding the UC7 functionality and settings refer the documents available on our website www.temperzone.biz : -...
Page 2
An air conditioning unit control device and system protection that responds to external temperature control signals to dictate unit operation. Introduced into temperzone air cooled and water sourced models from 2013, replacing the previous OUC4 & HWP Protection Board Controllers respectively. These are not an accessory.
This is only suitable for fixed speed compressor control and High/Medium/Low fan speed control - not variable speed. Only voltages of 12V or 24Vac can be utilised. The UC7 will not tolerate mains voltage being applied. TZT-100 Temperature Controller Can control variable capacity compressor (digital directly and inverter via a third party driver board).
Page 4
Inputs Available Terminals Power 230VAC L/N + Earth Conventional Thermostat/Controller: - (High/Med/Low/Common) Hi/Me/Lo/C1 (Compressor/Heat/Common) Comp/Heat/C2 Only voltages of 12V or 24Vac can be utilised. HP Switch In#1 LP Switch In#2 Analogue 0 – 10Vdc Not labelled Modbus/BMS RS485#1Slave B/A/Ground Modbus/BMS RS485#2 Master +12Vdc/B/A/Ground DRED D1/D2/D3/Sc Ground...
Conventional Temperature Controller E.g. SAT-2.1 24Vac Version or BMS with switched outputs Only voltages of 12V or 24Vac can be utilised - the UC7 will not tolerate mains voltage being applied. Connected using multiple wires for all functions, (High/Medium/Low Fan, Compressor and Heat functions), to a terminal strip on the unit.
Fault Codes Display Meaning Low pressure protection is active High pressure protection is active HI-t High temperature protection is active FROSt Indoor coil frost protection is active HI-SL High suction line temperature protection is active Lo-dSH Low discharge superheat protection active Hi-dSH High discharge superheat protection active Overload protection is active: “IN #2”...
Page 8
Diagnosing and Troubleshooting Fault Codes Display
Meaning
Possible
c ause
Possible
r emedy
LP
Low
p ressure
Lack
o f
r efrigerant
Check
f or
l eaks
a nd
r epair,
a pply
c orrect
protection
...
Page 9
Display
Meaning
Possible
c ause
Possible
r emedy
FROSt
Indoor
c oil
f rost
Air
f ilter
b locked
Clean
o r
r eplace
a ir
f ilter
protection
...
Page 10
Display
Meaning
Possible
c ause
Possible
r emedy
OL
Overload
Indoor
f an
i s
o verloaded
Check
i ndoor
f an.
C heck
a irflow
i s
n ot
protection
...
Page 11
Remove
m ains
p ower,
e nsure
DIP
s witches
humidity
UC7
c ircuit
b oard
i s
t horoughly
dry,
r e-‐apply
p ower
F27
...
Page 12
Display
Fault
Possible
c ause
Possible
r emedy
F34
Problem
w ith
Transducer
w ires
s wapped
Correct
t ransducer
w iring
readings
f rom
t he
Transducers
...
Page 13
Three speed fan: HI/ME/LO relay outputs Single speed fan: ME relay output 0-10V EC fan: V2 output Select this option when the UC7 does not control the indoor fan. Reserved: Do not select Electronic expansion valve operating mode No electronic expansion valves (e.g. accurators, TX valves...).
Page 14
Table
2 ,
S tandard
D IP
s witch
f unctions
f or
s witches
1 4,
1 5
a nd
1 6.
Switch Function Quiet mode option Disabled Enabled (D1 input) Switches 14 and 15 MUST be set to OFF.
Need help?
Do you have a question about the UC7 and is the answer not in the manual?